Loading...
HomeMy WebLinkAboutOrdinance - 2009-O0033 - Amending Chapt 6; Adoption Of 2006 International Plumbing Code - 04/09/2009First: Reading April 9,. 2009 Itea No. 5.10 ORDINANCE NO. 2009-o0033 Second Reading April 27,. 2009 Item No. 5.28 N ORDINANCE AMENDING CHAPTER 6 OF THE CODE OF ORDINANCES F THE CITY OF LUBBOCK, TEXAS WITH REGARD TO ADOPTION OF THE 006 INTERNATIONAL PLUMBING CODE AND PROVIDING FOR CERTAfN MENDMENTS THERETO TO MEET LOCAL CONDITIONS; PROVIDING A ENALTY; PROVIDING A SAVINGS CLAUSE; AND PROVIDING FOR UBLICATION. HEREAS the City Council of the City of Lubbock, Texas deems it in the best terest of the health, safety, and welfare of the citizens of Lubbock to adopt the 2006 ternational Plumbing Code for the City of Lubbock with certain amendments ereto to meet local conditions; NOW THEREFORE: E IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF LUBBOCK: ECTION 1. THAT Chapter Section 6-2 of the Code of Ordinances of the City of 1 ubbock is hereby amended to read as follows: Sec. 6-2. Scope. The provisions of this code shall apply to the construction, alteration, movement, enlargement, replacement, repair, equipment, use and occupancy, location, maintenance, removal and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures, as well as the construction, alteration, movement, enlargement, replacement, repair, maintenance, removal and demolition of building systems governed by the specific technical codes referenced in the following Articles of this Chapter: Article II: The 2003 International Building Code, as amended; Article III: The 2006 International Plumbing Code, as amended; Article IV : The 2006 International Mechanical Code, as amended; Article V: The 2003 ICC Electrical Code, as amended; Article VI : The 2006 International Residential Code, as amended; Article VII: The 2006 International Fuel Gas Code, as amended; Article VIII: The 2003 International Energy Conservation Code, as amended; Article IX: The 2003 International Existing Buildings Code, as amended. ECTION 2. THAT Chapter 6, Article III, Section 6-81 through 6-100 of the Code of rdinances of the City of Lubbock is hereby deleted in its entirety and the following ubstituted therefore: ARTICLE III. DIVISION 1. GENERAL Sec. 6-81. International Plumbing Code adopted. The 2006 Edition of the International Plumbing Code, as published by the International Code Council, Inc., as hereinafter amended, including Appendices C, D, E, F and G, is hereby adopted as the plumbing code of the City of Lubbock, Texas. A copy of said plumbing code is attached hereto and incorporated herein as though set out herein in detail. References to the Plumbing Code in this chapter shall mean the 2006 Edition of the International Plumbing Code. One copy of the 2006 International Plumbing Code shall be filed with the City Secretary and a copy shall be maintained in the office of the City Building Official. All such copies, with the amendments thereto, shall be open to public inspection during the usual hours of business of the offices where they are maintained. DIVISION 2. SUPPLEMENTAL ADMINISTRATIVE PROVISIONS Sec. 6-82. Coordination of administrative provisions. The administrative provisions contained in Chapter 6, Article I of this Code of Ordinances are applicable to this Article; however, for purposes of administering provisions related more specifically to the regulation of plumbing systems installation, these supplemental administrative provisions have been provided. Except as amended or supplemented within this Division 2, the entire text of Chapter 1 of the 2006 International Plumbing Code is deemed to be incorporated herein as though set out herein in detail. Where a conflict arises between a provision contained within this Division 2 and Chapter 6, Article I of this Code of Ordinances, it is the intent that the more specific govern, as determined by the Building Official. Sec. 6-83. Fee schedule. Section 106.6.2 is hereby amended by inserting thefollowingfee schedule: PLUMBING FEES* $0.05 per sq. ft. of gross floor area under roof, $30.00 New Construction: minimum. (Where more than one inspection is required, an additional fee of$15.00 shall be assessed for each additional inspection) Additions to floor As for new construction area Alterations & $2.00 per $1,000.00 valuation, $30.00 minimum (Where remodeling (no more than one inspection is required, an additional fee of change in building $15.00 shall be assessed for each additional inspection) area): (See Note 3) Total re-plumb: As for new const. Miscellaneous pennits for new installations, replacement and repair of: $30.00 (Where more than one inspection is required, an Water heaters, additional fee of$15.00 shall be assessed for each water lines, sewer additional inspection) lines, gas lines, water softeners, Service line tap fees, or adjustments in grade, where irrigation systems, needed, may involve extra fees. Contact the appropriate fixed appliances, utility department. fixtures, etc. requiring inspection approval: Pennit fees, work commencing prior to permit approval: Renewal of expired or As for building pennit fees (see Article I), except that involuntarily permit fee calculations shall be based on this section. terminated penn its: Permit transfer fee: Re-inspection Fees: *The fees in this schedule are all-inclusive for the collective plumbing work (water, DWV, & fuel gas) performed in a building; they are NOT intended to be charged in addition to the fees specified in Article VII of this Chapter. Sec. 6-84. Administrative amendments and cross-references to Article I. The following administrative provisions within Chapter 1 of the International Plwnbing Code are hereby stricken, and the corresponding provisions within Article I (General Provisions) of this Code of Ordinances shall govern. as indicated in Table 6-84 below: TABLE 6-84 ADMINISTRATIVE PROVISIONS CROSS-REFERENCE 2006 I Section Heading/Subject I Refer to Internatio Lubbock nal Code of Mechanic Ordinances al Code Chapter Section Sed ion 106.6.3 Fee refunds 6-80B 108.4 Violation penalties 6-80DD 108.5 Stop work orders 6-80EE 109.1 Means of appeal 6-80V through through 6-80Z 109.7 DIVISION 3. TECHNICAL AMENDMENTS Sec. 6-85. Definitions for sections 6-100.1--6-100.3. For the purposes of section 6-1 00.1, section 6-1 00.2 and section 6-1 00.3 of the Code of Ordinances ofthe City of Lubbock, and section 312.9 and section 608 of the 2006 International Plumbing Code, sections P2503.7 and P2902 of the 2006 International Residential Code, and the USC Manual of Cross- Connection Control, American Water Works Association Ml4 Manual, the following definitions shall apply. In the event of a conflict between the definitions set forth below and the definitions provided in the 2006 International Plumbing, 2006 International Residential Codes, the USC Manual of Cross-Connection Control, American Water Works Association M 14 Manual, for the purposes of sections 6-1 00.1, 6-1 00.2 and 6-1 00.3 of the Code of Ordinances of the City of Lubbock, the definitions set forth below shall control. (1) Air gap shall mean the unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet conveying water to a tank, fixture, receptor, sink, or other assembly and the flood level rim of the receptacle. The vertical, physical separation must be at least twice the diameter of the water supply outlet, but never less than 1.0 inch. An air gap may also be a horizontal space between two pipes at no less than 6.0 inches. (2) Approved shall mean accepted by the authority responsible as meeting an applicable specification stated or cited in sections 6-85, 6-100.2 through 6-100.3 or as suitable for the proposed use. (3) Auxiliary water supply shall mean any water supply on or available to the premises other than the purveyor's approved public water supply that presents a potential contamination hazard of the public water system. These auxiliary waters may include water from another purveyor's public water supply or any natural source(s) such as a well, spring, river or stream or used waters, or industrial fluids. These waters may be contaminated or polluted or they may be objectionable and constitute an unacceptable water source over which the water purveyor does not have sanitary control. (4) Backjlow shall mean the undesirable reversal of flow in a public water distribution system as a result of a cross connection. (5) Backjlow prevention assembly shall mean an approved assembly to counteract backpressure or prevent backsiphonage. (6) Backflow prevention assembly test and maintenance report shall mean the report required for each backflow prevention assembly upon initial installation and periodically thereafter as required, giving evidence that the backflow prevention assembly has been properly selected based on the degree of hazard, and has been properly installed and tested in accordance with applicable standards, and showing the results of this test The completed form will be forwarded to the water purveyor for documentation and annual record keeping. (7) Backflow prevention assembly tester, backjlow tester, or general tester shall mean a backflow assembly device tester who is qualified to test backflow prevention assemblies on any domestic, commercial, industrial or irrigation service (excepting firelines). This person must be licensed by TCEQ and registered with the City. (8) Backpressure shall mean pressure created by any means in the water distribution system, which by being in excess of the pressure in the water supply mains causes a potential backflow condition. (9) Backsiphonage shall mean the backflow of potentially contaminated water into the potable water system as a result of the pressure in the potable water system falling below atmospheric pressure of the plumbing fixtures, pools, tanks or vats connected to the potable water distribution piping. ( 1 0) Building official shall mean the officer charged with the enforcement of the building, plumbing, mechanical, electrical, fuel gas, and energy conservation codes of the City, or his duly authorized representative. For pwposes of sections 6-85, 6- 100.2 through 6-100.3, all state-licensed plwnbing inspectors under the supervision of the building official are his duly authorized representatives. (11) Bypass arrangements shall mean any jwnper connections, removable section, unions, swivels or change-over devices and other temporary or permanent devices through which or because of which backflow can occur. (12) Contamination shall mean an impairment of the quality of the potable water that creates an actual hazard to the public health through poisoning or through the spread of disease by sewage, industrial fluids or waste. (13) Cross connection shall mean a physical connection or bypass arrangement between a public water system and either another supply of unknown or questionable quality, or another source that may contain contaminating or polluting substances, any source of water treated to a lesser degree in the treatment process, or any steam, gas or chemical system. (14) Cross-connection control device shall mean any nationally approved or recognized device placed upon any connection, physical or otherwise, between a potable water supply system and any plumbing fixture or any tank, receptacle, equipment or device, which is designed to prevent nonpotable, used, unclean, polluted and contaminated water, or other substance, from entering into any part of such potable water system under any condition or set of conditions. (15) Cross connections-controlled shall mean a connection between a public water system and a nonpublic water system with an approved backflow prevention assembly properly installed and maintained so that it will continuously afford the protection commensurate with the degree of hazard. (16) Cross-connection control by containment shall mean the installation of an approved backflow prevention assembly at the water service connection to any customer's premises, where it is physically or economically unfeasible to find and permanently eliminate or control all cross connections or potential contamination hazards, within the customer's water system; or it shall mean the installation of an approved backflow prevention assembly on the service line leading to and supplying a portion of a customer's water system where there are cross connections or potential contamination hazards, that cannot be effectively eliminated or controlled at the point of the cross connection. ( 17) Customer/property owner shall mean the owner, as determined by the real property records of Lubbock County, Texas, or the agent of the owner in responsible charge of the subject premises. For purposes of sections 6-85, 6-100.2 through 6- 100.3, a licensed plumber and/or irrigator shall be deemed to be an agent of the owner when performing work under the scope of sections 6-85, 6-100.2 through 6-100.3 pursuant to a plumbing and/or irrigation permit. ( 18) Customer service inspection shall mean an inspection designed to detect any actual or potential point of contamination of the potable water system and/or cross-connection hazards. (19) Degree of hazard shall mean the nonhealth hazard or health hazard classification that shall be attached to all actual or potential cross connections. a. Nonhealth hazard shall mean a cross connection or potential cross connection involving any substance that generally would not be a health hazard but would constitute a nuisance or be aesthetically objectionable, if introduced into a public water supply. b. Health hazard shall mean the classification assigned to a cross connection or potential contamination hazard or other situation involving any substance that can cause illness, death, spread of disease or has a high probability of causing such effects if introduced into the potable drinking water supply. (20) Double check valve backjlow assembly (DCVA), double check assembly, and double check (DC) shall mean an assembly consisting of two independently acting, approved check valves, including tightly closing resilient seated shutoff valves attached at each end of the assembly and fitted properly located resilient seated test cocks. This assembly shall only be used to protect against a nonhealth hazard. (21) Fireline tester shall mean a tester who is qualified to test backflow prevention assemblies on firelines. This person must be licensed by TCEQ and registered with the City. (22) Licensed professional shall mean any individual, or their representative, that must maintain a license obtained through a professional licensing board in order to conduct their business under state law. (23) Nonpotable water shall mean water not safe for drinking, personal or culinary utilization. (24) Pollution shall mean an impairment of the quality of the potable water to a degree that does not create a hazard to the public health but that does adversely and unreasonably affect the aesthetic qualities of such potable water for domestic use. (25) Point of use isolation shall mean the appropriate backflow prevention within the consumer's water system at the point at which the actual or potential cross connection exists. (26) Potable water shall mean water free from impurities present in amounts sufficient to cause disease or harmful physiological effects and conforming to the bacteriological and chemical quality requirements of the Public Health Service Drinking Water Standards or the regulations of any public health authority having jurisdiction over such matters. (27) Potential contamination hazard shall mean a condition which, by its location, piping or configuration, has a reasonable probability of being used incorrectly, through carelessness, ignorance, or negligence, to create or cause to be created a backflow condition by which contamination can be introduced into the public water supply. Examples of potential contamination hazards are: a. bypass arrangements; b. jumper connections; c. removable sections or spools; and d. swivel or changeover assemblies. (28) Public Health Service Drinking Water Standards shall mean the standards set forth in 30 TAC 290 Subchapter F, as may be amended from time to time. (29) Reduced pressure principle backflow prevention assembly (RP BA), reduced pressure principle assembly, RPZ or RP assembly shall mean a backflow prevention device consisting of two independently acting check valves, internally force- loaded to a normally closed position and separated by an intermediate chamber (or zone) in which there is an automatic relief means of venting to the atmosphere, internally loaded to a normally open position between two tightly closing shutoff valves and with a means for testing for tightness of the checks and opening of the relief means. (30) Repair of an irrigation system shall mean the reconstruction or renewal of any part of an existing irrigation system, including without limitation, installation of a backflow prevention device, adding additional irrigation zones, reparation of a main irrigation line and valve replacement. For the purpose hereof, the replacement of a control box or sprinkler head(s) shall not be deemed to be a repair. ( 31) Service connection shall mean the point of deli very where the water purveyor loses control over the water. (32) Used water shall mean any water supplied by a water purveyor from a public water system to a consumer's water system after it has passed through the point of delivery or service connection and is no longer under the sanitary control of the water purveyor. (3 3) Water purveyor shall mean the director in charge of the water department of the City of Lubbock, who is vested with the authority and responsibility for the implementation of an effective cross-connection control program and for the enforcement of the provisions of sections 6-85, 6-100.2 through 6-100.3. Sec. 6-86. Pipes through or under footings or foundation waDs. Section 305.5. is hereby amended to read as follows: 305.5 Pipes through or under footings or foundation walls. Any pipe that passes through a foundation wall shall be provided with a pipe sleeve two pipe sizes greater than the pipe passing through the wall. If a pipe passes under a footing and is not in contact with the footing, then a sleeve or a relieving arch may be omitted, where approved by the Building Official. Sec. 6-87. Over-excavation. Section 306.2. 1. is hereby amended to read as follows: 306.2.1 Over-excavation. Where trenches are excavated below the installation level of the pipe such that the bottom of the trench does not form the bed for the pipe, the trench shall be backfilled to the installation level of the bottom of the pipe placed in layers of 6 inches ( 152 mm) maximum depth and such backfill shall be compacted after each placement. The backfill material may consist of sand or fine gravel, or excavated material that complies with Section 306.3. Sec. 6-88. Drainage and vent water test. Section 312. 2. is hereby amended to read as follows: 312.2 Drainage and vent water test. A water test shall be applied to the drainage system either in its entirety or in sections. If applied to the entire system, all openings in the piping shall be tightly closed, except the highest opening, and the system shall be filled with water to point of overflow. If the system is tested in sections, each opening shall be tightly plugged except the highest openings of the section under test, and each section shall be filled with water, but no section shall be tested with less than a five: foot head of water above floor height. In testing successive sections, at least the upper I 0 feet of the next preceding section shall be tested so that no joint or pipe in the building, except the uppermost 10 feet of the system, shall have been submitted to a test of less than a five-foot bead of water above floor height. The water shall be held kept in the system, or in the portion under test, for at least 15 minutes before inspection starts. The system shall then be tight at all points. Sec. 6-89. Gravity sewer test. Section 312. 6. is hereby amended to read as follows: 312.6 Gravity sewer test. Gravity sewer tests shall consist of plugging the end of the building sewer at the point of connection with the public sewer, filling the building sewer with water, testing with not less than a 5-foot head of water and maintaining such pressure for 15 minutes. Sec. 6-90. Sheet lead. Section 402.4. is hereby amended to read as follows: 402.4 Sheet lead. Sheet lead for pans shall not weigh less than two and one-half (2-1/2)_pounds per square foot coated with an asphalt paint or other approved coating. Se~. 6-91. Sheet lead. Section 417.5.2.3. is hereby amended to read as follows: 417.5.2.3. Sheet lead. Sheet lead shall not weigh less than two and one-half (2 Y:z) pounds per square foot coated with an asphalt paint or other approved coating. The lead sheet shall be insulated from conducting substances other than the connecting drain by 15-pound asphalt felt or its equivalent. Sheet lead shall be joined by burning. Sec. 6-92. Discharge. Section 504. 6, items 2, 3 and 5 are hereby amended to read as follows: 2. Discharge through an air gap or air break located in the same room as the water heater. 3. Not be smaller than the diameter of the outlet of the valve served and shall discharge full size to the air gap or air break. 5. Discharge to the floor, to an indirect waste receptor or to the outdoors. Where discharging to the outdoors in areas subject to freezing, discharge piping shall be first piped to an indirect waste receptor through an air gap or air break located in a conditioned area. Sec. 6-93. Water hammer. Section 604. 9. is hereby amended to read as follows: 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. An air chamber or a water-hammer arrestor shall be installed where quick-closing valves are utilized, unless otherwise approved. Water- hammer arrestors shall be installed in accordance with the manufacturer's specifications. Water-hammer arrestors shall conform to ASSE 1010. Sec. 6-94. Solvent cementing. Section 605.22. 2. is hereby amended to read as follows: 605.22.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A purple primer that conforms to ASTM F 656 shall be applied. Clear primer in lieu of purple is acceptable where joints are accessible. Solvent cement not purple in color and conforming to ASTM D 2564 or CSA CAN/CSA-Bl37.3 shall be applied to all joint surfaces. The joint shall be made while the cement is wet and shall be in accordance with ASTM D 2855. Solvent-cement joints shall be permitted above or below ground. Sec. 6-95. Location of full-open valves. Section 606.1. is hereby amended to read as follows: 606.1 Location of full-open valves. Full open valves shall be installed in the following locations: 1. On the building water service pipe from the public water supply. 2. On the water distribution supply pipe at the entrance into the structure if the water meter is more than 1 00 feet from the building. 3. On the water supply pipe to a gravity or pressurized water tank. 4. On the water supply pipe to every water heater. Sec. 6-96. Location of shut off valves. Section 606.2. is hereby amended to read as follows: 606.2 Location of shut off valves. Shutoff valves shall be installed in the following locations: I. On the fixture supply to each plumbing fixture in other than bathtubs and showers in one-and two-family and multiple-family residential occupancies, and other than in individual sleeping units that are provided with unit shutoff valves in hotels, motels, boarding houses and similar occupancies. 2. On the water supply pipe to each appliance or mechanical equipment. Sec. 6-97. Slope of horizontal drainage pipe. Table 704.1 is hereby amended to read as follows: TABLE 704.1 SLOPE OF HORIZONTAL DRAINAGE PIPE Size (inches) 2 1/2 or less 3 to 5 6 or larger Sec. 6-98. Solvent cementing. Minimum slope (inch per foot) 114 118 l/16 Section 705.8.2. is hereby amended to read as follows: 705.8.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A purple primer that conforms to ASTM F 656 shall be applied. Clear primer in lieu of purple primer is acceptable where joints are accessible. Solvent cement not purple in color and conforming to ASTM D 2564 CSA CAN/CSA-8137.3, CSA CAN/CSA-8181.2 or CSA CAN/CSA-BV 182.1 shall be applied to all joint surfaces. The joint shall be made while the cement is wet and shall be in accordance with ASTM D 2855. Solvent-cement joints shall be permitted above or below ground. Sec. 6-99. Solvent cementing. Section 705.14. 2. is hereby amended to read as follows: 705.14.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A purple primer that conforms to ASTM F 656 shall be applied. Clear primer in lieu of purple primer is acceptable where joints are accessible. Solvent cement not purple in color and conforming to ASTM D 2564 CSA CAN/CSA-8137.3, CSA CAN/CSA-B181.2 or CSA CAN/CSA-8Vl82.1 shall be applied to all joint surfaces. The joint shall be made while the cement is wet and shall be in accordance with ASTM D 2855. Solvent-cement joints shall be permitted above or below ground. Sec. 6-99A. Installation of fittings. Section 706. 3. is hereby amended to read as follows: 706.3 Installation of fittings. Fittings shall be installed to guide sewage and waste in the direction of flow. Change in direction shall be made by fittings installed in accordance with Table 706.3. Change in direction by combination fittings, side inlets or increasers shall be installed in accordance with Table 706.3 based on the pattern of flow created by the fitting. Double sanitary tee patterns shall not receive the discharge ofback-to-back water closets and fixtures or appliances with pumping action discharge. Sec. 6-998. Building drains and sewers. Table 710.1(1) is hereby amended to read as follows: Table 710.1(1) BUILDING DRAINS AND SEWERS MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS CONNECTED TO ANY PORTION OF THE BUILDING DRAIN OR THE BUILDING SEWER, INCLUDING BRANCHES OF THE BUILDING DRAIN Diameter of pipe (inches) 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8 10 12 15 1/16 inch 620 1400 2500 3900 7000 Slope per foot 118 inch 36 180 390 700 1600 2900 4600 8300 For SI: 1 inch=25.4 mm, 1 inch per foot=0.8333 mrnlm 1/4 inch 1 3 21 24 42 216 480 840 1920 3500 5600 10,000 a. The minimum size of any building drain serving a water closet shall be 3 inches. Sec. 6-99C. Roof extension. Section 904.1 is hereby amended to read as follows: 112 inc 1 3 26 31 50 250 575 1000 2300 4200 6700 12,000 904.1 Roof Extension. All open vent pipes that extend through a roof shall be terminated at least 10 inches above the roof, except that where a roof is to be used for any purpose other than weather protection, the vent extensions shall be run at least 7 feet above the roof. Sec. 6-99D. Storm drainage-general (tests). Section 1101.4 is hereby amended to read as follows: 1101.4 Tests. The building storm drain shall be tested within the building only and shall not require 5-foot head, but roof drain level only. Sec. 6-99E. Combining storm with sanitary drainage. Section 1104.2. is hereby amended to read as follows: 1104.2 Combining storm with sanitary drainage. The sanitary and storm drainage systems of a structure shall be entirely separate. Sec. 6-99F. Size of combined drains and sewers. Section 1108.1 is hereby amended by deletion in its entirety: Sec. 6-99G. Medical gas certification. Section 1202 is hereby amended by adding a new section 1202.2, as follows: 1202.2 Certification required. A medical gas certification must be furnished to the building inspection department before a final will be approved. Sec. 6-99H through 6-100 (Reserved) ECTION 3. THAT Section 6-100.1 of the Code of Ordinances, City of Lubbock, exas, is hereby amended to read as follows: Sec. 6-100.1 Protection of water supply--General. Section 6-100.1, section 6-100.2, and section 6-100.3 of the Code of Ordinances of the City of Lubbock are intended to supplement the USC Manual of Cross-Connection Control, American Water Works Association Ml4 Manual, section 312.9, "Inspection and Testing of Backflow Prevention Assemblies," and section 608, ''Protection of Potable Water Supply" of the 2006 International Plumbing Code, as well as sections P2503.7 and P2902 of the 2006 International Residential Code, both codes having been previously adopted as a part of the Code of Ordinances of the City of Lubbock, Texas. In the event of any conflict between the USC Manual of Cross-Connection Control, American Water Works Association M14 Manual, sections 312.9 or 608 of the 2006 International Plumbing Code or sections P2503. 7 or P2902 of the 2006 International Residential Code and section 6-100.1, section 6-100.2, and section 6-1 00.3 of the Code of Ordinances of the City of Lubbock, Texas, the provisions of section 6-100.1, section 6-100.2, and section 6-100.3 of the Code of Ordinances of the City of Lubbock shall controL Section 6-100.1, section 6-100.2, and section 6-100.3 of the Code of Ordinances of the City of Lubbock shall be liberally construed to protect the public health and safety of the citizens of the City of Lubbock, Texas. ECTION 4: THAT Subsections 6-100.2(a) and 6-100.2(b) of the Code of rdinances, City of Lubbock, Texas are hereby amended to read as follows: (a) Responsibilities of water purveyor. (1) a. No water service connection to any premises shall be installed or maintained by the water purveyor unless the water supply is protected as required by state law, including without limitation, 30 TAC 290.44(h), 30 TAC 290.460), 30 TAC 290.47(i), 30 TAC 344.73 and 30 TAC 344.75, as same may be amended from time to time. Service of water, subject to the provisions of sections 6-100.1, 6-100.2, or 6-100.3 of the Code of Ordinances of the City of Lubbock, or sections 312.9 or 608 of the 2006 International Plumbing Code, or sections P2503. 7 or P2902 of the 2006 International Residential Code, as applicable, to any premises shall be discontinued by the water purveyor if a backflow prevention assembly required by sections 6-85, 6-100.2 through 6-100.3 is not installed properly, tested and maintained, or if it is found that a backflow prevention assembly has been removed, bypassed, or if an unprotected cross connection exists on the premises. Service will not be restored until such conditions or defects are corrected. b. For new facilities, permanent water service shall not be provided until all testable backflow prevention assemblies have been tested and are operational. Except in cases where the testing of backflow prevention assemblies must be delayed until the installation of internal production or auxiliary equipment, The City shall not approve any certificate of occupancy until all backflow prevention assemblies have been tested and are operational. (2) Customer service inspection. a. A customer service inspection for cross-cormection control shall be completed by the City water purveyor prior to providing continuous water service in each of the following circumstances: I. Water service to a newly constructed facility, in which case the customer service inspection shall be performed in conjunction with or near the same time as the plumbing final inspection conducted by the building official. 2. Any correction, addition or improvement to the water service or water distribution plumbing of any facility or premises, except for minor repair and maintenance work exempted from permitting by section 106.2 of the 2006 International Plumbing Code, or in cases where an approved RPBA backflow prevention device has been installed at the point of water service cormection such that premises' isolation is achieved, and said device has been verified as having been properly tested and maintained as provided herein. Where nonexempt plumbing work has been performed upon the water service or water distribution plumbing of any facility or premises, and approved premises isolation has been provided as described herein, the building official shall be solely responsible for ensuring compliance of any such work on the customer side of the backflow device. b. A permanent water service shall not be established with regard to a newly constructed facility until after the customer service inspection is completed. c. Temporary water service, for construction or other purposes, that is found to pose a potential cross-cormection threat to the potable water due to the unknown use of the water therefor, or other reasons or causes, shall be protected by an approved backflow prevention assembly. (3) If, in the judgment of the water purveyor or building official an approved backflow prevention assembly is required at the customer's/property owner's water service cormection; or, within the customer's/property owner's private water system for the safety of the public water system, the water purveyor or the designated agent shall: a. Give notice in writing to the customer/property owner to install an approved backflow prevention assembly(s) at specific location(s) at his/her expense, and depending on the severity of the threat to the public water supply, within the time frame required by the City and in all instances within thirty (30) days. b. In the case of any premises where, in the opinion of the water purveyor and/or building official, an imminent health threat is posed due to cross connection or a potential contamination hazard, water service to the facility may immediately be discontinued without prior written notice to customer/property owner. Although the City will attempt to provide notice as is reasonably practical, no notice shall be required prior to discontinuance. ( 4) Failure, refusal or inability on the part of the customer/property owner to install, have tested and maintain the backflow prevention assembly(s) shall be grounds for discontinuing water service to the premises until such requirements have been met as required by sections 6-82, 6-1 00.2 through 6-1 00.3. (5) Any reduction in water pressure caused by the installation ofbackflow prevention assembly devices shall not be the responsibility of the City. (b) Responsibilities ofthe customer/property owner. The customer's/property owner's system shall include those parts of the potable water conveyance facilities beyond the termination of the utility distribution system that are conveying potable water to the points of use of customer/property owner. (1) Backflow prevention assemblies shall be installed within the customer's/property owner's system at the customer's/property owner's expense at any time required by sections 6-100.1, 6-100.2, or 6-100.3 of the Code of Ordinances of the City of Lubbock and/or sections 312.9 or 608 of the 2006 International Plumbing Code, or sections P2503.7 or P2902 of the 2006 International Residential Code, or the USC Manual of Cross-Connection Control, American Water Works Association M14 Manual, as applicable. All backflow prevention devices must be installed and tested as required by: a. Section 6-100.1, section 6-100.2, and section 6-100.3 of the Code of Ordinances of the City of Lubbock; b. Section 312.9 and section 608 of the 2006 International Plumbing Code; and c. 30 TAC 290.44(h), 30 TAC 290.460) and 30 TAC 290.47(i). (2) It shall be the responsibility of the customer/property owner to verify that all applicable City plumbing and/or irrigation permits are obtained and that the customer/property owner, or licensed plumber or irrigator, as applicable, is in compliance with all of the provisions of those permits. In addition to the remedies provided herein, in the event the backflow prevention assembly is installed by a licensed professional, failure by such licensed professional to follow the provisions of such permit will result in written notice to the applicable state licensing agency, in addition to being a violation of sections 6-82, 6-100.2 through 6-100.3. (3) It shall be the responsibility of the customer/property owner and backflow prevention assembly tester performing the subject test(s) to send to the City the backflow prevention assembly test and maintenance records. These materials shall be delivered to the Water Purveyor Office of the City within ten ( 1 0) days of installation of the backflow prevention assembly. ( 4) The customer' slproperty owner's system shall be open for inspection at all reasonable times to authorized representatives of the City to determine whether cross connections or potential contamination hazards, including violations of sections 6-100.1, 6-100.2, or 6-100.3 of the Code of Ordinances of the City of Lubbock and/or sections 312.9 or 608 of the 2006 International Plumbing Code, or sections P2503.7 or P2902 of the 2006 International Residential Code, as applicable, exist. (5) If the customer or premises wherein potable water from the City is supplied or provided has an auxiliary water supply that is treated to a lesser degree than the public water supply or if the water quality is unknown, and which is either cross connected or poses a potential contamination hazard to the public water system, the public water system shall be protected against backflow or backsiphonage by an approved backflow prevention device. The described threat shall be deemed a health hazard when determining the type of approved backflow required. If the auxiliary water supply is used for irrigation purposes, the backflow assembly shall be subject to the requirements of30 TAC 344.75(c), as same may be amended from time to time. (6) In the event industrial fluids, any material dangerous to health or any other objectionable substances are handled in such a fashion as to create potential contamination hazard to the public water system, such condition shall be deemed a health hazard. The public water system shall be protected against backflow from the premises by installing an air gap, a reduced pressure principle backflow assembly, or such other backflow assembly device as may be required by 30 TAC 290.47(i), as same may be amended from time to time. See Attachment "A," to Ordinance No. 2007-00056 incorporated herein and made a part hereof for all purposes. (7) All new installations of or substantial alterations to fire suppression systems that utilize the City's public water supply shall have installed a U.L. approved backflow prevention device according to the degree of hazard that exists. For purposes of this section, a "substantial alteration" is deemed to be any alteration or expansion of the system that would trigger a requirement for review and approval by the authority having jurisdiction, normally being the City fire marshal. All fireline backflow prevention assemblies must be installed inside the building as determined by section 6-1 00.2 of the Code of Ordinances of the City of Lubbock. Upon the approved installation of the backflow prevention assembly, a cross-connection test report completed by a licensed fireline tester must be provided to the City as required by section 6-100.2(b)(3), above. (8) Subject to the conditions of this subsection (b)(8), a reduced pressure assembly shall be the minimum protection for fire hydrant water meters which are being used for a temporary water supply during construction or other uses which may pose a potential contamination hazard to the public water supply. OnJy City fire hydrant water meters with approved backflow prevention assemblies are allowed to be used within the City limits. Failure to comply with this subsection (b)(8) will result in the fire hydrant meter being removed from the premises by the water purveyor. (9) It shall be the duty of the customer/property owner at any premises where backflow prevention assemblies are installed to have certified inspections and operational tests made upon installation and at least once every three years in nonhealth hazard conditions. ln those instances where the water purveyor and/or building official of the City deems the potential backtlow to be a health hazard or a potential health hazard, certified inspections shall be required annually or at more frequent intervals as deemed necessary by the water purveyor. All inspections and tests of backflow prevention assemblies shall be at the expense of the customer/property owner and shall be performed by a backflow tester who is licensed with the Texas Commission on Environmental Quality and registered with the water purveyor and meeting all conditions and criteria of section 6-100.1, section 6-100.2, and section 6-100.3 of the Code of Ordinances of the City of Lubbock. I (10) It shall be the responsibility of the customer/property owner that all irrigation systems installed after the effective date hereof and for an existing system in the event of a repair, shall have installed an approved backflow prevention assembly other than an atmospheric vacuum breaker (A VB), in the event an existing irrigation system is repaired. (11) It shall be the responsibility of the customer/property owner to have the backflow prevention assembly device tested as described in sections 6-82,6-100.2 through 6-100.3. The backflow prevention assembly shall be repaired, overhauled, or replaced at the expense of the customer/property owner whenever said assemblies are found to be defective. Water service shall not be restored until repairs are complete. ECTION 5: THAT Subsections 6-I00.3(a), 6-100.3(b) and 6-IOO(d) ofthe Code of rdinances, City of Lubbock, Texas are hereby amended to read as follows: Sec. 6-100.3. Same-Approved backflow prevention device assembly and installation. (a) Any backflow prevention assembly required by sections 6-100.1, 6- l 00.2, or 6-100.3 of the Code of Ordinances of the City of Lubbock, or section 312.9 or 608 of the 2006 International Plumbing Code, or sections P2503.7 or P2902 of the 2006 International Residential Code, or the USC Manual of Cross-Connection Control, American Water Works Association M 14 Manual, as applicable, shall be of a model and size approved by the water purveyor/building official or as approved by 30 TAC 290.47(i), as same may be amended from time to time. Backflow prevention devices must be approved by the City prior to installation. A plumbing permit is required in accordance with Section 6-39 of this article. The City shall determine the type and location of the backflow prevention assembly to be installed within the area served by the public water system. (b) The term "approved backflow prevention assembly" shall mean a backflow prevention assembly that has been manufactured and installed in full conformance with the standards specified within the 2006 International Plumbing Code and those established by the American Water Works Association (A WW A) and the USC Manual of Cross-Connection Control, American Water Works Association Ml4 Manual, titled: A WW A CSI 0 Standard for Double Check Valve Backflow-Prevention Assembly, and A WWA C511 Standard for Reduced-Pressure Backflow- Prevention Assembly, and have met completely the laboratory field perfonnance specifications of the Foundation for Cross-Connection Control and Hydraulic Research (FCCHR) and the University of Southern California (USC), "Specification of Backflow-Prevention Assemblies" -Sec. 10 of the most current issue of the Manual of Cross-Connection Control. (d) Backflow prevention assemblies, in addition to other requirements set forth in sections 6-100.1, 6-100.2, or 6-100.3 of the Code of Ordinances of the City of Lubbock, or section 312.9 or 608 of the 2006 International Plumbing Code, sections P2503. 7 or P2902 of the 2006 International Residential Code, or the USC Manual of Cross-Connection Control, American Water Works Association Ml4 Manual, shall be installed in accordance with subsections (1) through (9) below. The clearance standards set forth in subsections (1) through (9), below, shall apply to all assemblies installed in enclosures and meter boxes. ECTION 6. THAT violation of any provision of this ordinance shall be deemed a isdemeanor punishable as provided by Section 1-4 of the Code of Ordinances of the ity of Lubbock, Texas. ECTION 7. THAT should any paragraph, sentence, clause, phrase or word of this rdinance be declared unconstitutional or invalid for any reason, the remainder of his Ordinance shall not be affected thereby. ECTION 8. THAT the City Secretary of the City of Lubbock, Texas, is hereby uthorized and directed to cause publication of the descriptive caption of this rdinance as an alternative means of publication provided by law. AND IT IS SO ORDERED. assed by the City Council on first reading this 9th day of---=-_A,_pr_~_·l __ , 2009. assed by the City Council on second reading this 27thday of April , 2009. PPROVED AS TO CONTENT: IPC 2006 Ordinance_! .31.09