HomeMy WebLinkAboutOrdinance - 2006-O0050 - DROPPED- Did Not Go For A 2Nd Reading - 04/26/2006First Reading April 26, 2006 Item. No. 5.14 Second Reading May 18, 2006 Item. No. 2.4 ORDINANCE NO. 2006-oooso AN ORDINANCE AM:ENDING CHAPTER 6, ARTICLE II, OF THE CODE OF ORDINANCES OF THE CITY OF LUBBOCK, TEXAS ENT LED HBUILDING CODE" TO AMEND THE 2003 INTERNATIONAL BUILDING COD ITH REGARD TO REQUIRED FIRE SUPPRESSION SYSTEMS IN GROUP R OCC CIES; PROVIDING A SAVINGS CLAUSE; AND PROVIDING FOR PUBLICATION. WHEREAS, the City Council of the C y of Lubbock desires to amend the 2003 International Building Code with regard to fir suppression systems in Group R occupancies; NOW THEREFORE: BE IT ORDAINED BY THE CITY CO CIL OF THE CITY OF LUBBOCK: SECTION 1. THAT the Code of Ordi ances of the City of Lubbock is hereby amended by adding a new section, to be number Sec. 6-120, which said section reads as follows: "Sec. 6-120. IBC Sectio 503.1.5: Non-sprinkled group R-2 apartment occupancies. Add a new Section 503 '1.5 to read as follows: 503.1.5 Non·sprin ed group R-2 apartment occupancies. Group R-2 apartment buildings of two ories or less in height that are not protected throughout with an automatic fire su~ ression system in accordance with Section 903.2.7 shall be limited to the heights and eas specified in Table 503.1.5 in lieu of Table 503. Footnotes to Table 503.1.5 shall go em where in conflict with other provisions ofthis code." Add a new Ta le 503.1.5, to read as follows: TABLE 503.1.5 ALLOWABLE HE GHT & BUILDING AREAS PER FLOOR FOR NON-SPRINKLED GROUP R-2 APARTMENT OCCUPANCIES eight limitations shown as stories and feet above grade plane. itations as determined b the de nition o "Area, buildin " oor TYPE OF CONSTRUCTION TYPE! TYPE II IYPEIII TYPE TYPEV IV A B A B A B HT A B Group ~----~~~--------~--------~--------~~--------~--------~~----~--------~----4 R-2 40 40 40 40 40 40 40 40 40 2 2 2 2 2 2 2 2 2 UL 29,900 13,500 9,100 13,500 9,100 13,500 10,500 6,000 a. ere of other than Type I Construction, group R2 apartment occupancies having m re than 3, 000 square feet of floor area above the first story shall be of not less than 1 our fire-resistive construction throughout, except that interior non load-bearing partitions within individual dwelling units, when such dwelling units are separated 1 from each other and from corridors by not less than 1-hour fire-resistive construction, may be constructed of 1. Noncombustible materials or fire-retardant treated w od in any construction type; 2. Combustible framing with noncombustible ma framing in Type III or V construction. b. Area increases due to frontage in accordance with Secti 506.2 are applicable only when at least 20' of permanent open space is provid around the entire perimeter of each building c. All portions of the building must be accessi e to fire department personnel in accordance with the International Fire Code d. Exterior wall openings are not permitted here the fire separation distance is less than 5 '; where openings are required t be protected due to horizontal separation distance, the cumulative area of sue openings shall not exceed the lesser of the requirements in Table 704.8 or 50% )/the total area ofthe wall in each story e. Exterior wall fire resistance rati s shall be not less than one hour where the fire separation distance is less than 0 '; Where Jess than 5 ', the rating shall be for a fire exposure from both sides SECTION 2. THAT the Code of ances of the City of Lubbock is hereby amended by adding a new sectio~ to be number Sec. 6-120.1, which said section reads as follows: "Section 6-120.1. me S tion 508.4: Parking beneath Group R. Amend Section 508.4 t include an exception to read as follows: Exception: Group -2 apartment occupancies not provided with an approved automatic fire suppression sy, tern throughout." SECTION 3. THAT the ode of Ordinances of the City of Lubbock is hereby amended by adding a new section, t be numbered Sec. 6-120.2, which said section reads as follows: "Section 6-1 0.2. IBC Section 508.5: Group R-2 buildings of Type IliA construction. Amend Sect on 508.5 to include an exception to read as follows: : Group R-2 apartment occupancies not provided with an approved automatic ssion system throughout." SECTION 4. T T the Code of Ordinances of the City of Lubbock is hereby amended by adding a new tio~ to be numbered Sec. 6-120.3, which said section reads as follows: "Sec on 6-120.3. IBC Section 508.6: Group R-2 buildings of Type IIA construction. Ame d Section 508.6 to include an exception to read as follows: 2 Exception: Group R-2 apartment occupancies not provided with an ap fire suppression system throughout." SECTION 5. THAT the Code of Ordinances of the City ofLubboc ·s hereby amended by adding a new section, to be numbered Sec. 6-120.4, which said tion reads as follows: "Section 6-120.4. IBC Section 508.7.1 Fire separ 'on. Amend Section 508.7.1 by adding a sentence the end of the paragraph to read as follows: Group R-2 apartment occupancies not ovided with an approved automatic fire suppression system throughout are no permitted to have an open parking garage beneath the Group R-2 fire area." SECTION 6. THAT the Code ofOrdin ces of the City of Lubbock is hereby amended by adding a new section, to be numbered ec. 6-121, which said section reads as follows: "Sec. 6-12l.IBC Section 7 7.4.1: Draftstopping materials. Amend Section 717.4.1 to ead as follows: 717.4.1 Draftstoppin materials. Materials utilized for draftstopping of attic spaces shall comply with Sec ton 71 7. 3.1, except as indicated in Section 71 7 .4.2 below. " ode of Ordinances of the City of Lubbock is hereby amended by adding a new section, to numbered Sec. 6-121.1, which said section reads as follows: "Sec. 6-121.1. C Section 717.4.2: Groups R-1 and R-2. Amend Section 717.4.2 to read as follows: 717.4.2 Gro ps R-1 and R-2. Draftstopping shall be provided in attics, mansards, overhangs o other concealed roof spaces of Group R-2 buildings with three or more dwelling ts and less than three stories, and in all Group R-1 buildings. Draftstopping shall be ins lied above, and in line with, sleeping unit and dwelling unit separation walls that do n t extend to the underside of the roof sheathing above. Where required, draftstopp ng shall be constructed in accordance with Section 710, and shall be tightly fitted to e roof sheathing above and the ceiling below. When draft stopping is provided in Group R-1 and R-2 (other than one and two story apartment buildings), the materials shall co ist of one layer of 5/8" gypsum wallboard applied to both sides of a roof truss or other stantial framing." 3 Exceptions: 1. Where corridor walls provide a sleeping unit or dwelling unit sep stopping shall only be required above one of the corridor walls. 2. Draft stopping is not required in buildings equipped throughout sprinkler system in accordance with Section 903.3.1.1. 3. In occupancies in Group R-2 that do not exceed four stories · height, the attic space shall be subdivided by draft stops into areas not exceedin ,000 square feet or above every two dwelling units, whichever is smaller. 4. Draft stopping is not required in buildings equipp throughout with an automatic sprinkler system in accordance with Section 9 .3.1.2 provided that automatic sprinklers are also installed in attics and combus · le concealed spaces. SECTION 8. THAT the Code of Ordinances of the Ci of Lubbock is hereby amended by adding a new section, to be numbered Sec. 6-122, w ch said section reads as follows: "Sec. 6-122. IBC Section 903.2.7: Gro p R.. Amend Section 903.2. 7 to read as fo ows: 903.2. 7 Group R.. An autom · sprinkler system installed in accordance with Section 903.3 shall be provided throu out every Group R-2 apartment building three or more stories in height and in eve Group R-1, R-2 (other than one and two story apartments), R-3, and R-4 occupancy any height. Mixed occupancies of any height containing a Group R-1 or R-2 fire ea shall be protected by an automatic sprinkler system in accordance with Sectio 903.3.1.1. This section does not apply to one and two-family dwellings and multipl single-family dwellings (townhouses) not more than three stories in height with a sep ate means of egress covered by the International Residential Code.'' SECTION 9. THAT Code of Ordinances of the City of Lubbock is hereby amended by adding a new section, be numbered Sec. 6-122.1, which said section reads as follows: "Sec. 6-122 .• IBC Section 903.3.1.2: NFPA 13R sprinkler systems. Amend Se ion 903.3.1.2 to read as follows: 903.3.1. NFPA 13R sprinkler systems. Where allowed in Group R-2 apartment buildin s three or four stories in height, or in Group R-1, R-2 (other than one and two story artments), R-3 or R-4 occupancies up to and including four stories in height, auto tic sprinkler systems may be installed throughout in accordance with NFP A 13R. ,, SECTION 0. THAT the Code of Ordinances of the City of Lubbock is hereby amended by adding a ne section, to be numbered Sec. 6-123, which said section reads as follows: 4 "Sec. 6-123. IBC Section 1015.3: Exterior egress balcony incre Add an exception to Section 1015.3 to read as follows: Exception: Group R-2 apartment occupancies not tected throughout with an approved automatic fire suppression system ... SECTION 11. THAT the Code of Ordinance of the City of Lubbock is hereby amended by adding a new section, to be numbered Sec. 6-3.1, which said section reads as follows: "Sec. 6-123.1. IBC Table 1016 •• Corridor Fire-Resistance Rating. Add a new footnoted to Tab 1 OJ 6.1 to read as follows: d. Corridors in Group R-apartment occupancies not protected throughout with an approved automatic fir suppression system as allowed by other provisions of this Code shall be provided wi corridors of one hour of fire resistance." SECTION 12. THAT th Code of Ordinances of the City of Lubbock is hereby amended by adding a new section, t e numbered Sec. 6-123.2, which said section reads as follows: "Sec. 6-123 •• IBC Section 1025.1: Emergency escape and rescue; General. Amend Ex ption 2 to read as follows: r than Group R-2 occupancies not provided with an approved fire suppression system oughout and Group R-3 occupancies as applicable in Sections 101.2, sleep· grooms provided with a door to a fire-resistance rated corridor having access to two mote exits in opposite directions." SECTION 13. THAT should any paragraph, sentence, clause, phrase or word of this Ordinance be declar <i unconstitutional or invalid for any reason, the remainder of this Ordinance shall not be affect d thereby. SECTI N 14. THAT the City Secretary is hereby authorized to cause publication of the descrip ·ve caption of this Ordinance as an alternative method provided by law. 5 AND IT IS SO ORDERED. Passed by the City Council on first reading this 26th day of7_---=:=.c;..::.==--~' 2006. Passed by the City Council on second reading this 18th y of , 2006. MARC MCDOUGAL, MAYOR ATTEST: Rebecca Garza, City Secretary 6 Page 1 of 1 Linda Hart -Second Reading Ordinances From: Trenia Harris To: Hart, Unda Date: 9/1/2006 4:11PM Subject: Second Reading Ordinances As per Steve O'Neal, the following Ordinances 2006-00050 and 2006-00051 will not go for a second reading. They have been dropped. Thanks, Trenia Harris Building Inspection Department X3191 file://C:\Documents and Settings\17273\Local Settings\Temp\GW} 00002.HTM 9/1/2006