Loading...
HomeMy WebLinkAboutOrdinance - 2019-O0091 - Adoption Of 2015 International Residential Code - 07/23/2019 First Reading Second Reading July 9, 2019 July 23,2019 Item No. 7.20 ORDINANCE NO. 2p 1ppA I Item No. 6.29 AN ORDINANCE AMENDING ARTICLE 28.14 OF THE CODE OF ORDINANCES OF THE CITY OF LUBBOCK,TEXAS WITH REGARD TO ADOPTION OF THE 2015 INTERNATIONAL RESIDENTIAL CODE AND PROVIDING FOR CERTAIN AMENDMENTS THERETO TO MEET LOCAL CONDITIONS; PROVIDING A PENALTY; PROVIDING A SAVINGS CLAUSE; AND PROVIDING FOR PUBLICATION. WHEREAS the City Council of the City of Lubbock,Texas deems it in the best interest of the health, safety, and welfare of the citizens of Lubbock to adopt the 2015 International Residential Code for the City of Lubbock with certain amendments thereto to meet local conditions;NOW THEREFORE: BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF LUBBOCK: SECTION 1. THAT Chapter 28, Articles 28.14.001 through 28.14.004 of the Code of Ordinances of the City of Lubbock is hereby amended to read as follows: Sec.28.14.001 Adopted The 2015 edition of the International Residential Code (third or later printing), as published by the International Code Council, Inc., as hereinafter amended, including appendices A-D, G, N, and P, and excluding part VIII (Electrical) and appendices E, F, H-M, O and Q-U is hereby adopted as the residential code of the City of Lubbock, Texas. A copy of said code is attached hereto and incorporated herein as though set out herein in detail. References to the Residential Code in this chapter shall mean the 2015 edition of the International Residential Code.One copy of the 2015 International Residential Code shall be filed with the city secretary and a copy shall be maintained in the office of the city building official.All such copies, with the amendments thereto, shall be open to public inspection during the usual hours of business of the offices where they are maintained. Sec. 28.14.002 Coordination of administrative provisions The administrative provisions contained in chapter 28,articles 28.01 through 28.08 of this Code of Ordinances are applicable to this article; however, for purposes of administering provisions related more specifically to the regulation of one- and two-family dwelling construction, these supplemental administrative provisions have been provided.Except as amended or supplemented within sections 28.14.002 and 28.14.003, the entire text of chapter 1 of the 2015 International Residential Code is deemed to be incorporated herein as though set out herein in detail. Where a conflict arises between a provision contained within sections 28.14.002 and 28.14.003 and chapter 28,articles 28.01 through 28.08 of this Code of Ordinances, it is the intent that the more specific govern,as determined by the building official. 1 Sec. 28.14.003 Supplemental administrative provisions (a) Administrative amendments and cross-references to articles 28.01 through 28.08.The following administrative provisions within chapter 1 of the International Residential Code are hereby stricken, and the corresponding provisions within articles 28.01 through 28.08 of this Code of Ordinances shall govern, as indicated in table 28.14.003 below: TABLE 28.14.003(a) ADMINISTRATIVE PROVISIONS CROSS-REFERENCE 2015 Section Refer to Lubbock International Heading/Subject Code of Residential Ordinances Code Section Chapter Section R105.2 Work exempt from 28.05.019 permit R106.1 & Submittal documents 28.05.003, R106.1.1 and information on 28.05.004 construction documents R110 Certificate of 28.06.007 Occupancy R112 Board of Appeals 2.03.491 through 2.03.495 R113.4 Violation penalties 28.02.006 R114 Stop work orders 28.02.007 (b) Schedule of permit fees. Section R108.2 is hereby amended to read as follows: R108.2 Schedule of permit fees. On buildings, structures, electrical, gas, mechanical and plumbing systems or alterations requiring a permit, a fee for each permit shall be paid as required, as established in the annual operating budget subsequent to review and adjustment by the City Council pursuant to Section 1.03.004 of the Lubbock Code of Ordinances. . Pending the adoption of the annual operating budget for the ensuing fiscal year, the following fee schedule shall be applicable: CITY OF LUBBOCK CONSTRUCTION PERMIT FEE SCHEDULE One and Two-Family Dwellings Shaded areas do notapply) PERMIT/P COMMERCIAL RESIDENTIAL(1- ROJECT/F 2 Family Dwellings EE & Ancilla 2 CATEGOR Y BUILDING PERMITS New All buildings: $0.20 New home or Construction per sq. ft. of gross duplex: $0.11 per floor under roof sq. ft. of conditioned space Accessory and/or unconditioned buildings: $0.11 per sq. ft. under roof Additions to As for new As for new floor area construction construction Alterations & $2.25 per$1,000.00 As for new remodeling construction construction, $50.00 (no change in valuation, $30.00 minimum building minimum area): Demolition $50.00 All others $50.00 (generic) Minimum $50.00 (Where more than one inspection is building required, an additional fee of$15.00 shall be permit fee assessed for each additional inspection) (all classes, unless noted otherwise) Advance 10% of building Not Applicable Plan Review permit fee, $30.00 Fee: min., $100.00 max., to be credited toward final review fee Plan Review 25%of building Fee (payable pen-nit fee with permit): Review fee, None first revision: Review fee, 5% of building second and permit, $30.00 subsequent minimum, $100.00 revisions: maximum(in advance 3 Review fee, 5% of building change permit, $30.00 orders and minimum, $100.00 other maximum (in modifications advance) House/buildi $50.00 (Building permit fees will apply to final set ng moving up in city limits, but are not the responsibility of permit: the moving contractor) CITY OF LUBBOCK CONSTRUCTION PERMIT FEE SCHEDULE One and Two-Family Dwellings Shaded areas do nota PERMIT/P COMMERCIAL RESIDENTIAL (1- ROJECT/F 2 Family Dwellings EE & Ancillary) CATEGOR Y BUILDING PERMITS Permit fees, One location involved: 200% of normal building work permit fee. commencing prior to Two locations involved: 200% of normal permit fee permit for first site, 300% of normal permit fee for second approval: site. Three or more locations involved: As above, except that the third and subsequent sites shall each be assessed fees of 400% of the normal permit fees. Re-roofing, demolition, and house-moving fees shall be the greater of $100.00 or 200% of the normal permit fee for each site involved. Investigative inspection fees of $60.00, as deemed necessary Renewal of One-half of original building permit fees expired permit: Renewal of Greater of$100.00 or 200% of the original permit involuntarily fees; Where utilities have been terminated due to terminated illegal occupancy, the fees shall be paid prior to re- permit: establishment of utility service 4 Permit Scope of work unchanged from original pen-nit: transfer fee: Original fee, not to exceed $250.00 Scope of work varies from original permit: Fees as for new construction Investigative inspection fees of $60.00 may be necessary Re- First re-inspection: $30.00 inspection Fees: Second re-inspection: $45.00 Third re-inspection: $60.00 Fourth and subsequent re-inspections: $75.00 CITY OF LUBBOCK CONSTRUCTION PERMIT FEE SCHEDULE One and Two-Family Dwellings (Shaded areas do notapply) PERMIT/P COMMERCIAL RESIDENTIAL ROJECT/F (1-2 Family EE Dwellings & CATEGOR Ancillary) Y BUILDING PERMITS Investigative Single $60.00; Subsequent buildings $25.00 inspection fee: 5 Certificates Where associated with Not Applicable of an active building Occupancy permit for a new or building, remodel, Completion: renovation or addition: No Charge Exiting buildings: Replacement of lost Certificate: $30.00 Reissue due to a change in occupancy classification, or the expiration of two years since the last inspection of the premises: Single building: $60.00 inspection fee plus $30.00 C.O. fee; Multiple buildings: $60.00 inspection fee for the first building plus $30.00 C.O. fee; Subsequent buildings: $25.00 inspection fee plus $15.00 C.O. fee (c) Inspections. Section R109 is hereby amended to read as follows: R109.1 Types of inspections. For on-site construction,from time to time the building official, upon notification from the permit holder or his agent,shall make or cause to be made any necessary inspections and shall either approve that portion of the construction as completed or shall notify the permit holder or his or her agent wherein the same fails to comply with this or other applicable codes and requirements. R109.1.1 Foundation inspection. Inspection of the foundation shall be made after poles or piers are set or trenches or basement areas are excavated and any required forms erected and any required reinforcing steel is in place and supported prior to the placing of 6 concrete. The foundation inspection shall include excavations for thickened slabs intended for the support of bearing walls,partitions, structural supports,or equipment and special requirements for wood foundations. R109.1.2 Plumbing, mechanical, gas and electrical systems inspection. Rough inspection of plumbing, mechanical, gas and electrical systems shall be made prior to covering or concealment, before fixtures or appliances are set or installed,and prior to framing inspection. Exception: Ground-source heat pump loop systems tested in accordance with Section M2105.1 shall be permitted to be backfilled prior to inspection. R109.1.3 Floodplain inspections. For construction in areas prone to flooding as established by Table R301.2(l), upon placement of the lowest floor, including basement, and prior to further vertical construction, the building official shall require submission of documentation, prepared and sealed by a registered design professional, of the elevation of the lowest floor, including basement, required in Section R324. R109.1.4 Frame and masoga inspection. Inspection of framing and masonry construction shall be made after the roof, masonry; all framing, fire stopping, draft stopping and bracing are in place and after the plumbing, mechanical and electrical rough inspections are approved. R109.1.5 Other inspections. In addition to the called inspections above, the building official may make or require any other inspections to ascertain compliance with this code and other laws enforced by the building official. R109.1.5.1 Fire-resistance-rated construction inspection. Where fire-resistance-rated construction is required between dwelling units or due to location on property, the building official shall require an inspection of such construction after all lathing and/or wallboard is in place,but before any plaster is applied,or before wallboard joints and fasteners are taped and finished. R109.1.5.2. Reinforced masonry, insulating concrete form (ICF) and conventionally-formed or earth-formed concrete wall inspection. Reinforced masonry walls, insulating concrete form (ICF) walls and conventionally formed or earth formed concrete walls shall be inspected after plumbing, mechanical and electrical 7 systems embedded within the walls, and reinforcing steel is in place and supported and prior to placement of grout or concrete. Inspection shall verify the correct size, location, embedment depth, clearances, spacing and lapping of reinforcing and other embedded items. For masonry walls, inspection shall also verify that the location of grout cleanouts and size of grout spaces comply with the requirements of this code, and that grout pour heights are not exceeded. R109.1.6 Final inspection. Final inspection shall be made after the permitted work is complete and prior to occupancy. R109.2 Inspection agencies. The building official is authorized to accept reports of approved agencies, provided such agencies satisfy the requirements as to qualifications and reliability. Where the use of inspection agencies is desired or contemplated,the permittee shall request approval of said agencies sufficiently in advance of the need for the subject inspection(s). R109.3 Inspection requests. It shall be the duty of the permit holder or their agent to notify the building official that such work is ready for inspection. It shall be the duty of the person requesting any inspections required by this code to provide access to and means for inspection of such work. R109.4 Approval required. Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the building official. The building official upon notification shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or shall notify the permit holder or an agent of the permit holder wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the building official. Section 28.14.004 'Technical amendments (a) Definitions. Section R-202 is hereby amended by adding a new definition as follows: Engineered fill. Soil used for fill or backfill that has been placed,compacted and tested in accordance with the specifications of the structural or geotechnical engineer of record, or, where such specifications do not exist, that has been classified, placed, compacted and tested to a minimum 95% of standard proctor density in accordance with accepted industry standards. 8 (b) Climatic and geographic design criteria. Section R301.2(1) is hereby amended by insertion of the following local climatic and geographic design criteria into table R301.2(1): TABLE 1001.2.(1) CLIM1IAnC AND GEOGRAPHIC DESIGN CRITERIA WIND DESIGN SUulECr ro DAMAGE PRONI GROUND SEISMIC' WIN'I M ICEBARRIER AIR MCAN UN. No FLOOD SNOW Tulognp DESIGN Print DESIGN UNUERLAVM1IL"N f:IiEEZING ANNUAL LOAD Spced hical CATEGORY Weanccriag filo '1'cnn 1, TEMP TRI;QU I REM HAZARDS INDEX 7["IP paphl cfrcctt dcplhIs psr 11,f Na A Modcrale 1:' o ldl-1 I N Urgrecs Nu Sce Nutc 1 172 )Cg— Note I:See Lubbock Alnnieiryll Cede Amdc 31193 (c) Exterior walls. Section R302.1 is hereby arnended by the addition of a new exception #6 to read as follows: 6. In garden home developments with easements specifically allowing overhangs to project into adjacent lots, overhangs may project a maximum of 2 feet across the property line. Such overhangs must be one-hour fire resistive construction and be decked with fire retardant treated decking. The overhang shall not be equipped with soffit vents or penetrations. (d) Exterior walls (Table R302.1(2). Table R302.1(2) is hereby amended to read as follows: TABLE R302.1(2) EXTERIOR WALLS MINIMUM FIREW MINIMUM FIRE. FXERIOR WALL F.LIiMGiN'I' RESISTANCE RATING SEPARATION DISTANCE 1-hour in accordance with Fire-resistance rated ASTM L•' 119 or UL 263 Less than 5 feet Walls with exposure from both sides Non tire-resistance rated 0 Hours 5 leet or realer Not allowed NIA Less than 2 Icer Projections fire-resistance rated I hour on the underside"I' 2 fleet to less than 3 feet Non tire-resistance rated 0 Hours _ 3 feet Not allowed _ NIA Less than 3 Feet OI)cnilir:s in Maximum 25%ofwall 0]-lours 3 feet Walls area Unlimited 0 flours 5 feet Comte with Section Penetrations All IZ302-4 Less than 3 feet None re uired 3 feet or renter a. Rooreave fire-resistance rating shall be permitted to be reduced to 0 lours on the underside of the eave if fireblocking is provided from the wall rop plate io the underside of the roof sheathing. b. Ronfeavc lire-resistance rating shall be permitted to be reduced to 0 hours on the underside of the eave provided that gable vent openings are not installed. (e) Opening protection. Section R302.5.1 is hereby amended to read as follows: R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings 9 between the garage and residence shall be equipped with solid wood doors not less than 1-3/8 inches (35 mm) in thickness, solid or honeycomb-core steel doors not less than 1-3/8 inches(35 mm)thick,or 20-minute fire-rated doors,equipped with a self-closing device or a hard-wired carbon monoxide alarm installed on the residence side of the garage door entrance to the structure. (f) Bathrooms. Section R303.3 is hereby amended to read as follows: R303.3 Bathrooms. Bathrooms, water closet compartments and other similar rooms shall be provided with aggregate glazing area in windows of not less than 3 square feet(0.279 m2), one-half of which must be openable. Exception: The glazed areas shall not be required where artificial light and a local exhaust system are provided.The minimum local exhaust rates shall be determined in accordance with Section M1507. Exhaust air from the space shall be exhausted directly to the outside, or into a ventilated attic at least 10" above the ceiling insulation line or to a soffit, gable or eave vent. (g) Mechanical ventilation. Section R303.4 is hereby deleted in its entirety. (h) Emergency escape and rescue required. Section R310.1 is hereby amended to read as follows: R310.1 Emergency escape and rescue required. Basements and attics with habitable space and every sleeping room shall have at least one operable emergency escape and rescue opening. Such opening shall open directly into a street, public alley, or other approved public way, or into a yard or court on the same property that opens to an approved public way. Where basements contain one or more sleeping rooms, emergency egress and rescue openings shall be required in each sleeping room, but shall not be required in adjoining areas of the basement. Where emergency escape and rescue openings are provided they shall have a sill height of not more than 44 inches (I 118 mm) above the floor or a permanent adjacent standing surface of not less than 36 x 36 inches. Where a door opening having a threshold below the adjacent ground elevation serves as an emergency escape and rescue opening and is provided with a bulkhead enclosure, the bulkhead enclosure shall comply with Section 310.3. The net clear opening dimensions required by this section shall be obtained by the normal operation of the emergency escape and rescue opening from the inside. Emergency escape and rescue openings with a finished sill height below the adjacent ground elevation shall be provided with a window well in accordance with Section 8310.2. Exceptions: 10 1. Basements used only to house mechanical equipment and not exceeding a total floor area of 200 square feet. 2. Basements not containing bathing facilities or designated as bedrooms may be provided with alternatives to emergency escape and rescue openings as follows: a. Basements not exceeding 500 square feet and designated for use as a storm shelter- No requirement. b. Basements not exceeding 800 square feet and designated for use as a storm shelter: i. Top of basement stairs to be located within 10 feet of an approved emergency escape and rescue opening, or within 20 feet where entirely protected by an approved one- hour fire rated corridor constructed in accordance with the International Building Code. For purposes of this section, "travel distance" shall mean the centerline of the shortest route that affords a minimum 36" wide unobstructed path of travel; ii. Basement and path of travel to an approved emergency escape and rescue opening to be protected by an NFPA 13D fire suppression system; iii. As otherwise approved by the Building Official. C. Basements of any size where the entire dwelling is provided with an automatic fire suppression system throughout in accordance with NFPA 13D- No requirement. (i) Automatic fire sprinkler systems. Section R313 is hereby deleted. 0) Storm shelters (General). Section R323.1 is hereby amended to read as follows: R323.1 Storm shelters (General). This section applies to the construction of storm shelters when constructed as separate detached buildings or when constructed as rooms within buildings for the purpose of providing safe refuge from storms that produce high winds, such as tornados and hurricanes. In addition to other applicable requirements in this code, such storm shelters shall be constructed in accordance with ICC/NSSA-500. 11 Exception: Basements designated as storm shelters for purposes of complying with exception 1 or 2 to section R310.1 need not be constructed in accordance with 1CC/NSSA-500. (k) Minimum size (of footings). Section R403.1.1 is hereby amended to read as follows: R403.1.1 Minimum size. Minimum sizes for concrete and masonry footings shall be as set forth in The City of Lubbock Residential Foundation Design Manual, adopted by reference as though fully set out herein. (1) Minimum depth. Section R403.1.4 is hereby amended to read as follows: Section R403.1.4. Minimum depth. All exterior footings shall be placed at least 12 inches (305 mm) below the undisturbed ground or engineered till (see definition) surface. Where applicable, the depth of footings shall also conform to sections R403.1.4.1 through R403.1.4.2. (m) Foundation anchorage. Section R403.1.6. is hereby amended by the addition of a third exception to read as follows: 3. Approved powder-actuated pins may be used in lieu of anchor bolts within twelve (12) inches of the joints of sole plates. (n) Foundation elevation. Section R403.1.7.3 is hereby amended to read as follows: R403.1.7.3. Foundation elevation. The lowest portion of a building finished floor elevation shall be installed no lower than that indicated in table R403.1.7.3 below: TABLE R403.1.7.3 Minimum Floor Elevations for Structures Relative to Lot Slope Elevation Min. Floor Min. Floor Difference- Elevation above Elevation above Top of curb top of curb when top of curb when to rear slope is from front slope is from rear property line to rear (inches) to front(inches) (inches) 0 12 12 6 10.5 13.5 12 9 15 18 8 16.5 24 6 18 30 1 6 1 19.5 36 6 21 12 The ground shall slope away from the structure in all directions as required elsewhere in this code; The minimum distance from the finished ground elevation to the top of the floor shall be eight(8)inches at all locations around the building; Minimum floor elevations. The minimum floor elevation shall be determined by using the top of the floor slab and shall be a minimum of six(6)inches above the calculated peak water surface elevation as determined by the city engineer,or that determined by Table 8403.1.7.3, whichever results in the more stringent requirement. It shall be the responsibility of the builder/contractor to provide the city building official with a survey certificate indicating the required finish floor elevation as determined by the surveyor.The required elevation shall be indicated on the construction plans and marked on the front street curb. Structures located in any floor hazard area shall comply with all F.E.M.A. regulations, which will supersede the above. Alternate elevations are permitted subject to the approval of the building official and city engineer, provided it can be demonstrated that required drainage to an approved point of discharge and away from the structure is provided at all locations on the site. (o) Concrete and masonry foundation walls. Sections R404.1.2.1 and R404.1.3 are hereby amended to read as follows: R404.1.2.1 Masonry foundation walls. Concrete masonry and clay masonry foundation walls shall be constructed as set forth in tables R404.1.1(1), R404.1.1(2), R404.1.1(3) or R404.1.1(4) and shall also comply with the applicable provisions of Sections R606. Where applicable, such walls shall be designed and constructed in accordance with the City of Lubbock Residential Foundation Design Manual, adopted by reference as though fully set out herein. In Seismic Design Categories D0, D 1 and D2, concrete masonry and clay masonry foundation walls shall comply with section R404.1.4. Rubble stone masonry foundation walls shall be constructed in accordance with sections R404.1.8 and R606.3.2. Rubble stone masonry walls shall not be used in Seismic Design Categories D0, D1 and D2. R404.1.2 Concrete foundation walls. Concrete foundation walls that support light-frame walls shall be designed and constructed in accordance with the provisions of this section,ACI 318,ACI 332,PCA 100,or the City of Lubbock Residential Foundation Design Manual, adopted by reference as though fully set out herein.Concrete foundation walls that support above- grade concrete walls that are within the applicability limits of section R608.2 shall be designed and constructed in accordance with the provisions of this section, ACI 318, ACI 332 or PCA 100. Concrete foundation walls that support above-grade concrete walls that are not within the applicability limits of section R608.2 shall be designed and constructed in accordance with the provisions of ACI 318,ACI 332 or PCA 100. When ACI 318, ACI 332, PCA 100 or the provisions of this section are used to design concrete foundation walls,project drawings,typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority. 13 (p) Concrete or masonry foundations. The exceptions to Section 405.1 are hereby amended to read as follows: Exceptions: 1. A drainage system is not required when the foundation is installed on well-drained ground or sand-gravel mixture soils according to the Unified Soil Classification System, Group I Soils, as detailed in table R405.1. 2. A drainage system is not required for a basement wall footing where the excavation for the basement wall does not result in a soil disturbance closer than three (3) feet to the exterior roof drip line and there is no evidence of groundwater infiltration. (q) Foundation water management. Section R406 is hereby amended by re-titling of the section and amended to read as follows: SECTION R406 FOUNDATION WATER MANAGEMENT 406.1 Concrete and masonry foundation dampness resistance. Except where required by section R406.2 to be made water-resistant, foundation walls that retain earth and enclose interior spaces and floors below grade shall be treated to resist dampness from the top of the footing to the finished grade. Masonry walls shall have not less than 3/8 inch (9.5 mm) portland cement parging applied to the exterior of the wall. The parging shall be treated in accordance with one of the following: 1. Bituminous coating, 2. 3 pounds per square yard (1.63 kg/M2) of acrylic modified cement. 3. 118-inch (3.2 mm) coat of surface-bonding cement complying with ASTM C 887. 4. Any material permitted in section R406.2. 5. Other approved materials or methods. Exception: Parging of unit masonry walls is not required where a material is approved for direct application to the masonry. 14 Concrete walls shall be treated for resistance to dampness by applying any one of the above listed materials or any one of the materials listed in section R406.2 to the exterior of the wall. 406.2 Concrete and masonry foundation water resistant barriers. In areas where a high water table or other severe soil-water conditions are known to exist, exterior foundation walls that retain earth and enclose interior spaces and floors below grade shall be provided with water resistant barriers from the top of the footing to the finished grade. Such barriers shall be in accordance with one of the following: 1. 2-ply hot-mopped felts. 2. 55 pound (25 kg) roll roofing. 3. 6-mil (0.15 mm) polyvinyl chloride. 4. 6-mil (0.15 mm) polyethylene. 5. 40-mil (1 mm) polymer-modified asphalt. 6. 60-mil (1.5 mm) flexible polymer cement. 7. 118-inch (3 mm) cement-based, fiber-reinforced waterproof coating. 8. 60-mil, (0.22 mm)solvent-free, liquid-applied synthetic rubber. 9. Other approved materials or methods. Exception: Organic solvent based products such as hydrocarbons, chlorinated hydrocarbons,ketones and esters shall not be used for ICF walls with expanded polystyrene form material. Plastic roofing cements, acrylic coatings, latex coatings, mortars and pargings are permitted to be used to seal ICF walls. Cold setting asphalt or hot asphalt shall conform to type C of ASTM D 449. Hot asphalt shall be applied at a temperature of less than 200 degrees Fahrenheit. All joints in membrane barriers shall be lapped and sealed with an adhesive compatible with the membrane. 406.3 Dampness resistance for wood foundations. 15 Wood foundations enclosing habitable or usable spaces located below grade shall be treated for resistance to dampness in accordance with sections R406.3.1 through R406.3.4. (r) Wood floor framing design and construction. Sections R502.2, R502.3,and R502.3.4 are hereby amended to read as follows: R502.2 Wood floor framing design and construction. Floors shall be designed and constructed in accordance with the provisions of this chapter, figure R502.2 and sections 8317 and R318 or in accordance with AF&PA/NDS. Basement floor-ceiling structural assemblies, where supporting a concrete floor slab above, shall be constructed in accordance with section R502.3 and figures R404.1.1(1), R404.1.1(2), R404.1.1(3), R404.1.1(4), R404.1.2(1) and/or R404.1.2(2), as applicable (figures contained in the City of Lubbock Residential Foundation Design Manual, adopted by reference as though fully set out herein). R502.3 Allowable joist spans. Spans for floor joists shall be in accordance with tables R502.3.1(1), R502.3.1(2) or R502.3.4, as applicable. For the most current data, other grades and species, or other loading conditions, refer to the latest AF&PA Span Tables for Joists and Rafters and/or current data available from the American Wood Council. (s) Joists supporting concrete slabs. Section R502.3 is hereby amended by the addition of a new sub-section R502.3.4, to read as follows: R502.3.4 Joists supporting concrete slabs. Joist assemblies supporting concrete floor-ceiling assemblies shall not exceed the load assumptions or joist spans indicated in table R502.3.4 within the City of Lubbock Residential Foundation Design Manual, adopted by reference as though fully set out herein. (t) Concrete floors on ground, General. Section R506.1 is hereby amended to read as follows: R506.1 Concrete floors on ground,General. Concrete slab-on-ground floors shall be a minimum 3.5 inches (89 mm) thick (for expansive soils, see section R403.1.8). The specified compressive strength of concrete shall be as set forth in section R402.2. To the extent applicable, concrete slab-on- ground floors shall be constructed in accordance with the City of Lubbock Residential Foundation Design Manual, adopted by reference as though fully set out herein. (u) Headers. Section R602.7 is hereby amended as follows: 16 R602.7 Headers. For header spans, see Tables R602.7(1)and R602.7(2)and R602.7(3)._For the most current data, other grades and species, or other loading conditions, refer to the latest AF do PA Span 1 ables fbr Joists and Rafters and/or current data available from the American Wood Council. (v) Flashing. Section R703.4 is hereby amended to read as follows: R703.4 Flashing. Approved corrosion-resistive flashing shall be provided in the exterior wall envelope in such a manner as to prevent entry of water into the wall cavity or penetration of water to the building structural framing components. Self-adhered membranes used as flashing shall comply with AAMA 711. The flashing shall extend to the surface of the exterior wall finish and shall be installed to prevent water from re-entering the exterior wall envelope. Approved corrosion-resistant flashings shall be installed at all of the following locations: 1. At top of all exterior window and door openings in such a manner as to be leak proof. 2. At the intersection of chimneys or other masonry construction with frame or stucco walls, with projecting lips on both sides under stucco copings. 3. Under and at the ends of masonry, wood or metal copings and sills. 4. Continuously above all projecting wood or composite trim. 5. Where exterior porches, decks or stairs attach to a wall or floor assembly of wood-frame construction. 6. At wall and roof intersections. 7. At built-in gutters. Exceptions: 1. The requirements of subparagraph 3 above may be omitted if a poured concrete foundation is used with a minimum 8-inch brick ledge drop. 2. The requirements of subparagraph 3 above may be omitted where soffits, porches or awnings serve as protection for the upper course of brick veneer. (w) Table 703.8.4 Tie Attachment and Airspace Requirements. Delete Table 703.8.4 and replace with the following: TABLE 703.8.4 TIE ATTACHMENT AND AIRSPACE REQUIREMENTS BACKING MINIMU MINIMU AIRSPACE AND TIE MTM. M TIE 17 FASTENE R. Wood stud 22 U.S.gage 6D-2"nail,ring backing with Nominal 1 in.between sheathing (0.0299 in.)x 7/8 shank or#8-2" corrugated sheet in.wide screw and veneer metal W1.7(No.9 U.S. Minimum Maximum 4- Wood stud gage;0.148 in.) 6D-2"nail,ring nominal I in. 1/2 in. backing with with hook shank or#8-2" between between metal strand wire embedded in screw sheathing and backing and mortar'oint veneer veneer W1.7(No.9 U.S. No. 10 screw Minimum Maximum 4- Cold-formed steel gage;a c 0.148 in.) extending through nominal 1 in. 1/2 in. stud backing with the steel framing with hook between between adjustable metal embedded in a minimum of sheathing and backing and strand wire mortar joint three exposed veneer veneer threads a. All ties and fasteners to be corrosion-resistant (x) Flashing. Section R703.8.5 is hereby amended to read as follows: R703.8.5 Flashing. Flashing shall be located beneath the first course of masonry within the first mortar bed joint above finished ground level above the foundation wall or slab and at other points of support, including structural floors, shelf angles and lintels that are not protected by eaves or patio covers when masonry veneers are designed in accordance with Section R703.8. See Section R703.8 and foundation details S1-S8 within the City of Lubbock Residential Foundation Design Manual for additional requirements. Exception: The requirements of R703.8.5 may be omitted if a poured concrete foundation is used with a minimum 8-inch brick ledge drop and all exterior window and door openings are caulked with sealant. (y) Weepholes. Section R703.8.6 is hereby amended to read as follows: R703.8.6 Weepholes. Weepholes shall be provided in the outside wythe of masonry walls at a maximum spacing of 33 inches (838 mm) on center. Weepholes shall not be less than 3/16 inch (5 mm) in diameter. Weepholes shall be located immediately above the flashing. Exception: The requirements of 8703.8.6 may be omitted if a poured concrete foundation is used with a minimum 8-inch brick ledge drop and all exterior window and door openings are flashed in accordance with Section R703.8.5,as amended. (z) Allowable ceiling Joist spans.Section R802.4 is hereby amended as follows: R802.4 Allowable ceiling joist spans. Spans for ceiling joists shall be in accordance with Tables R802.4(l)and R802.4(2).For the most current data, other grades and species, or other loading conditions, refer to the latest AF 18 & PA Span Tables for Joists and Rafters and/or current data available from the American Wood Council. (aa) Allowable rafter spans. Section R802.5 is hereby amended as follows: R802.5 Allowable rafter spans. Spans for rafters shall be in accordance with Tables R802.5.1(1) through R802.5.1(8). For the most current data, other grades and species, or other loading conditions, refer to the latest AF& PA Span Tables for Joists and Rafters and/or current data available from the American Wood Council. The span of each rafter shall be measured along the horizontal projection of the ranter. (bb) Ventilation required. Section R806.1 is hereby amended by adding the following exception after the section: Exception:Attic ventilation shall not be required when deemed unnecessary by the Building Official due to atmospheric or climatic conditions. (cc) Roof re-cover not allowed. Section R908.3.1.1 item no. 2 is hereby amended to read as follows: 2. Where the existing roof covering is wood shake, slate, clay, cement, asbestos-cement tile, or asphalt, fiberglass or composition shingles. (dd) Energy Efficiency (Chapter 11). The entire text of chapter 11 is hereby deleted and replaced with the following: Chapter 11- Energy Efficiency. One and two family dwellings shall comply with the applicable energy conservation provisions of the 2015 International Energy Conservation Code, as amended. (ee) Protection against physical damage. Section M1308.2.1 is hereby amended to read as follows: M1308.2.1 Protection against physical damage. In concealed locations where piping is installed through holes or notches in studs,joists, rafters or similar members less than 1.5 inches (38 mm) from the nearest edge of the member,the pipe shall be protected by steel shield plates. Such shield plates shall have a thickness on not less than 0.0575 inch (1.463 min) (No. 16 gage). Such plates shall cover the area of the pipe where the member is notched or bored. (ff) Sizing. Section M 1401.3 is hereby amended to read as follows: M1401.3. Sizing. Heating and cooling equipment shall be sized by the installing contractor based on building loads calculated in accordance with 19 ACCA Manual J or other approved heating and cooling calculation methodologies. (gg) Auxiliary and secondary drain systems. Section M1411.3.1 is hereby amended to read as follows: M1411.3.1 Auxiliary and secondary drain systems. In addition to the requirements of Section M1411.3, a secondary drain or auxiliary drain pan shall be required for each cooling or evaporator coil where damage to any building components will occur as a result of overflow from the equipment drain pan or stoppage in the condensate drain piping. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than 1/8 unit vertical in 12 units horizontal (1-percent slope). Drain piping shall be a minimum of 3/4-inch (19 mm) nominal pipe size. One of the following methods shall be used: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a minimum depth of 1.5 inches(38 min), shall not be less than 3 inches (76 mm) larger than the unit or the coil dimensions in width and length and shall be constructed of corrosion resistant material. Metallic pans shall have a minimum thiclaiess of not less than 0.0276-inch (0.7 mm) galvanized sheet metal. Nonmetallic pans shall have a minimum thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain line shall be connected to the drain pan provided with the equipment. Such overflow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drain pan at a higher level than the primary drain connection. 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a water level detection device conforming to UL 508 that will shut off the equipment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. (hh) Auxiliary drain pan. Section M 1411.4 is hereby amended to read as follows: M1411.4 Auxiliary drain pan. Category IV condensing appliances shall have an auxiliary drain pan where damage to any building component will 20 occur as a result of stoppage in the condensate drainage system. These pans shall be installed in accordance with the applicable provisions of Section M1411.3. (ii) Insulation of refrigerant piping. Section M1411.6 is hereby amended to read as follows: Section M1411.6. Insulation of refrigerant piping. Piping and fittings for refrigerant vapor(suction) lines shall be insulated with 318-inch (318") wall closed cell insulation having a thermal resistivity of at least R = 2.1) hr-ft2 -- P/BTU and having external surface permanence not exceeding 0.05 perm when tested in accordance with ASTM E 96. 0j) Locking port access caps. Section M1411.8 is hereby deleted. (kk) Outdoor discharge. Section M1501.1 is hereby amended to read as follows: M 1501.1 Outdoor discharge. The air removed by every mechanical exhaust system shall be discharged to the outdoors in accordance with Section M 1506.3. Air shall not be exhausted into an attic, soffit, ridge vent or crawl space. Exception: Whole-house ventilation-type attic fans and bathroom ventilation fans that discharge into a ventilated attic space of dwelling units having private attics shall be permitted. (11) Duct termination. Section M1502.3 is hereby amended to read as follows: M 1502.3. Duct termination. Exhaust ducts shall terminate on the outside of the building. Exhaust duct terminations shall be in accordance with the dryer manufacturer's installation instructions. If the manufacturer's instructions do not specify a termination location, exhaust ducts shall terminate not less than 3 feet in any direction from openings into buildings. Exhaust duct terminations shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Exception: Backdraft dampers shall not be required where exhaust ducts terminate vertically through the roof. (mm) Specified length. Section M1502.4.4.1 is hereby amended to read as follows: M1502.4.4.1 Specified length. The maxiinum length of the exhaust duct shall be 35 feet from the connection to the transition duct from the dryer to the outlet terminal. Where fittings are used, the maximum length of the exhaust duct shall be reduced in accordance with Table M 1502.4.4.1. 21 (nn) Recirculation of air. Section M1507.2 is hereby amended to read as follows: M 1507.2 Recirculation of air. Exhaust air from bathrooms and toilet rooms shall not be re-circulated within a residence or to another dwelling unit. Exhaust air from bathrooms and toilet rooms shall either discharge directly to the outdoors or into an attic space ventilated as required by Section R806 and at least 18 inches above the ceiling joists, or to a soffit or gable or eave vent. The tenninal end of the exhaust duct shall be permanently secured in place. (oo) Support. Section M1601.4.3 is hereby amended to read as follows: M1601.4.3 Support. Metal ducts shall be supported by 0.5-inch (12.7 min) wide 24-gage metal straps or 12-gage galvanized wire at intervals not exceeding 10 feet (3048 mm) or other approved means. Nonmetallic ducts shall be supported in accordance with the manufacturer's installation instructions. (pp) Location. Section M2006 is hereby amended by the addition of a new subsection M2006.5 to read as follows: M2006.5 Location. Pool heaters shall be located or protected to guard against accidental contact of hot surfaces by persons. Compliance with this section may be accomplished by installing pool and spa heaters in an equipment room or building, or by enclosure with a fence or other suitable barrier. (qq) Located at manifold. Section G2420.5.3. is hereby amended to read as follows: G2420.5.3 (409.5.3) Located at manifold. Where the appliance shutoff valve is installed at a manifold, such shutoff valve shall be located within 50 feet of the appliance served and shall be readily accessible and permanently identified. The piping from the manifold to within 6 feet of the appliance shall be designed, sized and installed in accordance with Sections G2412 through G2419. Shutoff valves located within attic spaces shall not be considered readily accessible. (rr) G2421.1 (410.1) Pressure regulators. Section G2421.1 is hereby amended to read as follows: A line pressure regulator shall be installed where the appliance is designed to operate at a lower pressure than the supply system. Access shall be provided to pressure regulators. Pressure regulators shall be protected from physical damage. Regulators installed on the exterior of the building shall 22 be approved for outdoor installation. All regulators must be installed near a walkway or an access point. (ss) Exhaust installation. Section G2439.3 is hereby amended to read as follows: G243 9.3 (614.4)Exhaust installation.Dryer exhaust ducts for clothes dryers shall terminate on the outside of the building and shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Ducts shall not be connected or installed with sheet metal screws or other fasteners that will obstruct the flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent or chimney. Clothes dryer exhaust ducts shall not extend into or through ducts or plenums unless properly sleeved with materials conforming to Section 602.2.1 of the International Mechanical Code (in the case of plenums), or with materials meeting the requirements for Class 0 or 1 duct materials(in the case of ducts). Backdraft dampers shall not be required for vertical terminations through roofs. (tt) Protection required. Section G2439.6 is hereby amended to read as follows: G2439.6(614.7)Protection required.Protective shield plates shall be placed where nails or screws from finish or other work are likely to penetrate the clothes dryer exhaust duct. Shield plates shall be placed on the finished face of all framing members where there is less than 1-114 inches between the duct and the finished face of the framing member. Protective shield plates shall be constructed of steel, and shall have a minimum thickness of 0.062 inch (1.6 mm). (uu) Length identification. Section G2439.7.5 is hereby amended to read as follows: G2439.7.5 (614.8.5) Length identification. Where the exhaust duct is concealed within the building construction and exceeds a total developed length of 35 feet,the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6 feet of the exhaust duct connection. (vv) Building sewer testing. Section P2503.4 is hereby amended to read as follows: Section P2503.4. Building sewer testing.The building sewer shall be tested by the insertion of a test plug at the point of connection with the public sewer and filling the building sewer with water,testing with not less than a five-foot head of water and be able to maintain such a pressure for fifteen (15)minutes. (ww) Rough plumbing. Section P2503.5.1 is hereby amended to read as follows: 23 P2503.5.1 Rough plumbing_,DWV systems shall be tested on completion of the rough piping installation by water or air with no evidence of leakage. Either test shall be applied to the drainage system in its entirety or in sections after rough piping has been installed, as follows: 1. Water test. Each section shall be filled with water to a point not less than 5 feet (3048 mm) above the highest fitting connection in that section, or to the highest point in the completed system. Water shall be held in the section under test for a period of 15 minutes. The system shall prove leak free by visual inspection. 2. Air test. The portion under test shall be maintained at a gauge pressure of 5 pounds per square inch (psi) (34 kPa) or 10 inches of mercury column (2488 Pa). This pressure shall be held without introduction of additional air for a period of 15 minutes. Exception: Air tests shall not be used on PVC piping if not approved by the piping manufacturer. (xx) Finished plumbing. Section P2503.5.2 is hereby amended to read as follows: P2503.5.2 Finished plumbing_ After the plumbing fixtures have been set and their traps filled with water,their connections shall be tested and proved gas tight and/or water tight as follows: 1. Water tightness. Each fixture shall be filled and then drained. Traps and fixture connections shall be proven water tight by visual inspection. 2. Gas tightness. When required by the Building Official,a final test for gas tightness of the DWV system shall be made by the smoke or peppermint test as follows: 2.1. Smoke test. Introduce a pungent, thick smoke into the system. When the smoke appears at vent terminals, such terminals shall be sealed and a pressure equivalent to a f- inch water column (249 Pa) shall be applied and maintained for a test period of not less than 15 minutes. 2.2. Peppermint test. Introduce 2 ounces (59 mL) of oil of peppermint into the system. Add 10 quarts (9464 mL) of hot water and seal all vent terminals. The odor of peppermint shall not be detected at any trap or other point in the system. (yy) Shower liner test. Section P2503.6 is hereby deleted. 24 (zz) Protection against physical damage. Section P2603.2.1 is hereby amended to read as follows: P2603.2.1 Protection against physical damage. In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1.5 inches (38 mm) from the nearest edge of the member, the pipe shall be protected by steel shield plates. Such shield plates shall have a thickness of not less than 0.0575 inch(1.463 mm) (No. 16 gage). Such plates shall cover the area of the pipe where the member is notched or bored. (aaa) Pan size and drain. Section P2801.6.1 is hereby amended to read as follows: P2801.6.1 Pan size and drain. The pan shall be not less than 1.5 inches (38 mm) deep and shall be of sufficient size and shape to receive all dripping and condensate from the tank or water heater. The pan shall be drained by an indirect waste pipe having a minimum diameter of 314 inch (19 mm) or the outlet diameter of the relief valve,whichever is larger. Piping for safety pan drains shall be of those materials listed in Table P2906.5, except that PVC meeting ASTM D 1785, D 2241 or D 2672 shall also be considered an acceptable material for this purpose. Where a pan was not previously installed, a pan drain shall not be required for a replacement water heater installation. (bbb) Water heaters installed in garages. Section P2801.7 is hereby amended to read as follows: P2801.7 Water heaters installed in garages. Water heaters having an ignition source shall be elevated such that the source of ignition is not less than 18 inches (457 mm) above the garage floor. Exceptions: 1. Elevation of the ignition source is not required for fuel gas-fired water heaters that are listed as flammable vapor ignition-resistant. (See Section G2408.2). 2. Electric water heaters are not required to be elevated,as the elements are not considered an ignition source. (ccc) Vacuum relief valve. Section P2804.7 is hereby amended to read as follows: P2804.7 Vacuum relief valve. Bottom fed tank-type water heaters and bottom fed tanks connected to water heaters shall have a vacuum relief valve installed that complies with ANSI 221.22. 25 Exception: Where such water heaters and tanks are part of a circulating hot water system and have a storage capacity of ten gallons or less. (ddd) Hose bibb bleed. Section P2903.8.5 is hereby deleted. (eee) Service valve. Section P2903.9.1 is hereby amended to read as follows: P2903.9.1 Service valve. Where indicated below, each dwelling unit shall be provided with an accessible main shutoff valve. The valve shall be of a full-open type having nominal restriction to flow. Service valves shall be installed in the following locations: 1. On the water service pipe from the public water supply at or near the water meter. 2. On the water service pipe at the entrance into the building(s) if the service valve required by (1) above is more than 100 feet from said building(s). 3. On the water supply pipe to a gravity or pressurized water tank. 4. On the water supply pipe to every water heater. (fff) Hose bibb. Section P2903.10 is hereby deleted. (ggg) Solvent cementing. Section P3003.9.2 is hereby amended to read as follows: P3003.9.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A purple primer that conforms to ASTM F 656 shall be applied. Clear primer in lieu of purple primer is acceptable where joints are accessible. Solvent cement not purple in color and conforming to ASTM D 2564 CSA CAN/CSA-B137.3, CSA CAN/CSA-B181.2 or CSA CAN/CSA-BV 182.1 shall be applied to all joint surfaces. The joint shall be made while the cement is wet and shall be in accordance with ASTM D 2855. Solvent-cement joints shall be permitted above or below ground. Exception: A primer shall not be required where all of the following conditions apply: 1. The solvent cement used is third-party certified as conforming to ASTM D 2564; and 26 2. The solvent cement is used only for joining PVC drain, waste and vent piping and fittings in non-pressure applications in sizes up to and including four inches(4") in diameter. (hhh) Horizontal to vertical (multiple connection fittings). Section P3005.1.1. is hereby amended to read as follows: P3005.1.1 Horizontal to vertical (multiple connection fittings)., Double fittings such as double sanitary tees and tee-wyes or approved multiple connection fittings and back-to-back fixture arrangements that connect two or more branches at the same level shall be permitted as long as directly opposing connections are the same size and the discharge into directly opposing connections is from similar fixture types or fixture groups. Double sanitary tee patterns shall not receive the discharge of back-to-back water closets and fixtures or appliances with pumping action discharge. (iii) (Cleanouts at) Building drain and building sewer iunction. Section P3005.2.7 is hereby amended to read as follows: P3005.2.3 (Cleanouts at) Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a two-way cleanout that is located at the junction or within ten feet(10') of developed length of piping upstream of the junction. Where the depth of the horizontal building drain at the two-cleanout location exceeds four feet(4'), a two pipe two-way cleanout shall be provided. For the requirements of this section, removal of a water closet shall not be required to provide cleanout access. (jjj) Permit requirements. A new Section P3010.1.1 is hereby added as follows P3010.1.1 Permit Requirements. A licensed plumbing contractor shall obtain a permit under this section prior to the work being performed. The permit application shall indicate if work in the city right-o-way will be necessary. If issued, the permit will grant the licensed plumbing contractor temporary permitted user status, as contemplated by Section 36.09 of the Lubbock Code of Ordinances, for limited access to the city right-of-way. Excavation in the city right-of-way subjects the permittee to all applicable requirements of Section 36.09, save and except the requirements for a separate right-of-way permit. The limited access is restricted to unpaved areas only and defined as an excavation that is hand-dug only (no mechanical excavation) and no more than 3 feet in width adjacent to the property line. The licensed plumbing contractor has the option of hiring a "permitted user"to perform the work in the public ROW. (kkk) Electrical. Part VIII, Chapters 34-43 inclusive, is hereby deleted. 27 (111) SWIMMING POOLS, SPAS AND HOT TUBS. A new chapter 34 is hereby created to read as follows: CHAPTER 34 SWIMMING POOLS,SPAS AND HOT TUBS 3401.1 General. The provisions of this chapter shall control the design and construction of swimming pools, spas and hot tubs installed in or on the lot of a one- or two-family dwelling. 3401.2 Pools in flood hazard areas. Pools that are located in flood hazard areas established by Table R301.2(1), including above-ground pools,on-ground pools and in-ground pools that involve placement of fill, shall comply with Section 3401.2.1 or 3401.2.2. Exception: Pools located in riverine flood hazard areas which are outside of designated floodways. 3401.2.1 Pools located in designated floodways. Where pools are located in designated floodways, documentation shall be submitted to the building official which demonstrates that the construction of the pool will not increase the design flood elevation at any point within the jurisdiction. 3401.2.2 Pools located where floodways have not been designated. Where pools are located where design flood elevations are specified but floodways have not been designated,the applicant shall provide a floodway analysis that demonstrates that the proposed pool will not increase the design flood elevation more than 1 foot (305 mm) at any point within the jurisdiction. Such analysis shall also demonstrate compliance with Section 30.03 of the Lubbock Code of Ordinances. SECTION 3402 —DEFINITIONS 3402.1 General. For the purposes of these requirements, the terms used shall be defined as follows and as set forth in Chapter 2. ABOVE-GROUND/ON-GROUND POOL. See "Swimming pool." BARRIER. A fence, wall, building wall or combination thereof which completely surrounds the swimming pool and obstructs access to the swimming pool. HOT TUB. See"Swimming pool." 28 IN-GROUND POOL. See "Swimming pool." RESIDENTIAL. That which is situated on the premises of a detached one- or two-family dwelling, or a one-family townhouse not more than three stories in height. SPA, NONPORTABLE. See "Swimming pool." SPA, PORTABLE. A nonpermanent structure intended for recreational bathing, in which all controls, water-heating and water-circulating equipment are an integral part of the product. SWIMMING POOL. Any structure intended for swimming or recreational bathing that contains water more than 24 inches (6 10 mm) deep. This includes in- ground, above-ground and on-ground swimming pools, hot tubs and spas. SWIMMING POOL, INDOOR. A swimming pool which is totally contained within a structure and surrounded on all four sides by the walls of the enclosing structure. SWIMMING POOL, OUTDOOR. Any swimming pool which is not an indoor pool. SECTION 3403 - SWIMMING POOLS 3403.1 In-ground pools. In-ground pools shall be designed and constructed in compliance with ANSI/NSP1-5. 3403.2 Above-ground and on-ground pools. Above-ground and on-ground pools shall be designed and constructed in compliance with ANSI/NSP1-4. 3403.3 Pools in flood hazard areas. In flood hazard areas established by Table R301.2(l), pools in coastal high hazard areas shall be designed and constructed in compliance with ASCE 24. SECTION 3404 - SPAS AND HOT TUBS 3404.1 Permanently installed spas and hot tubs. Permanently installed spas and hot tubs shall be designed and constructed in compliance with ANSI/NSPI-3. 3404.2 Portable spas and hot tubs. Portable spas and hot tubs shall be designed and constructed in compliance with ANSI/NSPI-6. 29 SECTION 3405-BARRIER REQUIREMENTS 3405.1 Application. The provisions of this appendix shall control the design of barriers for residential swimming pools, spas and hot tubs. These design controls are intended to provide protection against potential drownings and near- drownings by restricting access to swimming pools,spas and hot tubs. 3405.2 Outdoor swimming pool.An outdoor swimming pool, including an in- ground, above-ground or on-ground pool,hot tub or spa, shall be surrounded by a barrier which shall comply with the following: 1. The top of the barrier shall be at least 48 inches (1219 mm)above grade measured on the side of the barrier which faces away from the swimming pool. The maximum vertical clearance between grade and the bottom of the barrier shall be 2 inches (51 mm) measured on the side of the barrier which faces away from the swimming pool. Where the top of the pool structure is above grade, such as an above-ground pool,the barrier may be at ground level, such as the pool structure, or mounted on top of the pool structure. Where the barrier is mounted on top of the pool structure, the maximum vertical clearance between the top of the pool structure and the bottom of the barrier shall be 4 inches (102 mm). 2. Openings in the barrier shall not allow the passage of a 4-inch- diameter(102 mm) sphere. 3. Solid barriers which do not have openings, such as a masonry or stone wall, shall not contain indentations or protrusions,except for normal construction tolerances and tooled masonry joints. 4. Where the barrier is composed of horizontal and vertical members, and the distance between the tops of the horizontal members is less than 45 inches (1143 mm),the horizontal members shall be located on the swimming pool side of the fence. Spacing between vertical members shall not exceed 1-3/4 inches (44 mm) in width. Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 1-3/4 inches (44 mm) in width. 5. Where the barrier is composed of horizontal and vertical members, and the distance between the tops of the horizontal members is 45 inches (1143 mm) or more, spacing between vertical members shall not exceed 4 inches (102 mm). Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 1-3/4 inches (44 mm) in width. 6. Maximum mesh size for chain link fences shall be a 2-1/4 inch (57 mm)square, unless the fence has slats fastened at the top or the bottom which reduce the openings to not more than 1-3/4 inches (44 mm). 30 7. Where the barrier is composed of diagonal members, such as a lattice fence, the maximum opening formed by the diagonal members shall not be more than 1-3/4 inches (44 mm). 8. Access gates shall comply with the requirements of Items 1 through 7, and shall be equipped to accommodate a locking device. Pedestrian access gates shall open outward away from the pool, and shall be self-closing and have a self-latching device. Gates, other than pedestrian access gates, shall have a self-latching device. Where the release mechanism of the self-latching device is located less than 54 inches (1372 mm) from the bottom of the gate, the release mechanism and openings shall comply with the following: 8.1 The release mechanism shall be located on the pool side of the gate at least 3 inches (76 mm) below the top of the gate; and 8.2 The gate and barrier shall have no opening larger than '/2 inch (12.7 mm) within 18 inches (457 mm) of the release mechanism. 9. Where a wall of a divelling serves as part of the barrier, one of the following conditions shall be met: 9.1 The pool shall be equipped with a powered safety cover in compliance with ASTM F 1346; 9.2 Doors with direct access to the pool through that wall shall be equipped with an alarm which produces an audible warning when the door and/or its screen, if present, are opened. The alarm shall be listed and labeled in accordance with UL2017. The deactivation switch(es) shall be located at least 54 inches (1372 mm) above the threshold of the door; or 9.3 Other means of protection, such as self-closing doors with self-latching devices, with door opening devices located at 54" (13 72 mm) above the threshold of the door; which are approved by the governing body, shall be acceptable as long as the degree of protection afforded is not less than the protection afforded by Item 9.1 or 9.2 described herein. 10. Where an above-ground pool structure is used as a barrier or where the barrier is mounted on top of the pool structure, and the means of access is a ladder or steps: 10.1 The ladder or steps shall be capable of being secured, locked or removed to prevent access; or 10.2 The ladder or steps shall be surrounded by a barrier which meets the requirements of Items 1 through 9. When the ladder or 31 steps are secured, locked or removed, any opening created shall not allow the passage of a 4-inch diameter (102 mm) sphere. 3405.3 Indoor swimming pool. Walls surrounding an indoor swimming pool shall comply with Item 9 of Section 3405.2. 3405.4 Prohibited locations. Barriers shall be located to prohibit permanent structures, equipment or similar objects from being used to climb them. 3405.5 Barrier Exceptions. Spas or hot tubs with a safety cover which complies with ASTM F 1346 shall be exempt from the provisions of this appendix. SECTION 3406—ENTRAPMENT PROTECTION FOR SWIMMING POOL AND SPA SUCTION OUTLETS 3406.1 General. Suction outlets shall be designed and installed in accordance with APSP — 7. Exception: Portable spas and portable exercise spas listed and labeled in accordance with UL 156' or CSA C22.2 No. 218.1 SECTION 4. THAT violation of any provision of this ordinance shall be deemed a misdemeanor punishable as provided by Section 1.01.004 of the Code of Ordinances of the City of Lubbock, Texas. SECTION 5. THAT should any paragraph, sentence, clause, phrase or word of this Ordinance be declared unconstitutional or invalid for any reason, the remainder of this Ordinance shall not be affected thereby. SECTION 6. THAT the City Secretary of the City of Lubbock,Texas, is hereby authorized and directed to cause publication of the descriptive caption of this Ordinance as an alternative means of publication provided by law. SECTION 7. THAT this ordinance shall be effective thirty (30) days from its passage and publication. 32 AND IT IS SO ORDERED. Passed by the City Council on first reading this 9tli day of July , 2019. Passed by the City Council on second reading this 23rd_day of_ July , 2019. w-_ DAN POPE, MA OR ATTEST: Rebe t a Garza, City Secre ry APPRO ED AS TO CONTENT: Greg Zielinski, Inte im Chief Building Official APPROVED AS TO FORM: Amy,,Skffs, Assistai l -y 33