HomeMy WebLinkAboutResolution - 1393 - Contract-Cyclone Fence Sales-Fencing, LP&L Substation At Municipal Dr & Guava St - 05_12_1983RESOLUTION 1393 - 5/12/83
Bid 7349
jT
DGV:cl
RESOLUTION
BE IT RESOLVED BY THE CITY COUNCIL OF THE CITY OF LUBBOCK:
THAT the Mayor of the City of Lubbock BE and is hereby authorized and
directed to execute for and on behalf of the City of Lubbock a Contract with
Cyclone Fence Sales for a substation fence, as per specification number SE0001-
9-033183, pursuant to Bid Number 7349, said contract to be entered into by and
between said City as the prospective owner and Cyclone Fence Sales as the
contractor for such construction. The stated amount for such contract is
$8,260.00, attached herewith which shall be spread upon the minutes of the
Council and as spread upon the minutes of this Council shall constitute and be
a part of this Resolution as if fully copied herein in detail.
Passed by the City Council this 12th day of M'I V 1983.
_ v
ALA HENRY , MAYOR 0 TEN1
ATTEST:
E elyn Ga ga, City Secr ry-Treasurer
APPROVED AS TO CONTENT:
C
Carroll McDonald, Director of
Electric Utilities
APPROVED AS TO FORM:
Vandiv`ir, First Assistant City Attorney
RESOLUTION 1393.- 5/12/83
CONTRACT AGREEMENT ,
1
(EQUIPMENT)
THIS AGREEMENT, made and entered into this 12th day of May
19 83 , by and between The City of Lubbock, Texas acting through its Mayor and
City Council thereunto duly authorized so to do, Party of the First Part, and
hereinafter called the Purchaser, and Cyclone Fence Sales a
corporation of Texas , Party of the Second Part, and
hereinafter called the Contractor.
WITNESSETH:
THAT WHEREAS, the Purchaser has caused to be prepared, in accordance with
law, specifications, plans, and other contract documents for the work herein
described, and has approved and adopted said documents, and has caused to be
published, in the manner and for the time required by law, an advertisement
for and in connection with acquiring Substation Fence in accordance with
the terms of this Contract; and
WHEREAS, the said Contractor, in response to such advertisement, has
submitted to the Purchaser, in the manner and at the time specified, a sealed
proposal in accordance with the terms of said advertisement; and
WHEREAS, the Purchaser, in the manner prescribed by law, has publicly
opened, examined, and canvassed the proposals submitted in response to the
published invitation therefor, and as a result of such canvass has determined
and declared the aforesaid Contractor to be the best bidder for the said work
and has duly awarded to the said Contractor a contract therefor, for the sum
or sums named in the Contractor's proposal, a copy thereof being attached to
and made a part of this Contract.
NOW THEREFORE, in consideration of the compensation to be paid to the
Contractor and of the mutual agreements herein contained, the Parties to these
presents have agreed and hereby agree, the Purchaser for itself and its successors,
and the Contractor for itself, himself, or themselves, -or its, his, or their
successors and assigns, or its, his, or their executors and administrators, as
follows:
ARTICLE I. That the Contractor shall (a) Furnish all materials,.
supplies, and equipment specified and required to be incorporated in and form a
permanent part of the completed work; (b) Provide and perform all necessary
work; and, in a good, substantial, and workmanlike manner and in accordance
with the provisions of the General Conditions, and the Instructions to Bidders,
(which are attached hereto and made a part hereof) and in conformity with the
Specifications Number SE-0001-9-033183 (c) Execute and complete all work
included in and covered by the Purchaser's official award of this Contract to
the said Contractor, such award being based on the acceptance by the Purchaser
of the Contractor's proposal, or part thereof, as follows:
Substation Fence
l.r.� 1lLt 11. i }gat Lhe :: rc} user small pay to the Contractor for the
performance of the work embraced in this Contract, and the Contractor will
accept as full compensation therfor, the sum (subject to adjustment as pro-
vided by the Contract) of _ Eight thousand two hundred sixty dollars
($ 8,260.00 )
for all work covered by and included in the Contract award and designated in
the foregoing Article I.
ARTICLE III.- The Contractor shall proceed with the work to be performed
under the provisions of this Contract on, or within ten (10) days following,
the date of public acceptance.of the Contractor's proposal by the Purchaser.
Contractor shall not'delay the start of the work to be performed under the
provisions of this Contract except by written order from the Purchaser.
Contractor shall complete said work by July 1st, 1983
IN WITNESS WHEREOF, the Parties hereto have executed this Contract as of
day and year first written.
CITY OF LUBBOCK
BY: x/r,
�/✓
ATTEST: UMMMMM, 7
ALAN HENRY
Evelyn Ga fga, City4S46c ary-Treasurer
APPROVED AS TO CONTENT:
APPROVED AS TO FORM:
DONALD G. VANDIVER, Assistant':Clty:Attor ney
PARTY OF THE SECOND PART (CONTRACTOR)
ATTEST:
Secretary
BY:
Signature of Officer
Title
NOTE: This Contract must be signed by the President or Vice President of the
Contractor's firm and attested by the Secretary of the firm. If the Contract
is to be signed by any person other than the President or Vice President, then
a Board Resolution authorizing said person to sign and bind the firm must be
included with each copy of the Contract.
STANDARD CHAIN LINK FENCE SPECIFICATIONS
I. STYLE FENCE
Chain link fence with three strands of barbed wire on 450 extension arms.
Fence to be nine (9) feet high overall when erec'fed.
11. FABRIC '
Steel wire to be ninety-six (96) inches high, #9 gauge woven in a two (2)
inch mesh with barbed selvages top and bottom. The wire pickets shall stand
a minimum tensile strength -of 80,000 PSI based on a cross sectional area of
wire.
111. PROTECTIVE COATING
The chain link fabric shall be either galvanized after weaving or aluminum
coated. Galvanizing shall be 2 oz. per sq. ft. of area in accordance with
ASTM A392 Class 11. Aluminum coating shall be .40 oz. per sq. ft. of area
in accordance with ASTM A491-63-T.
IV. BOTTOM TENSION WIRE E BARBED WIRE
Steel barbed wire to be of 4 point pattern composed of two strands of 121
gauge line wires with 14 gauge barbs spaced on approximately five (5) inch
centers. Bottom tension wire shall be No. 7 gauge spring coil tension wire,
fastened to chain link fabric with No. 11 gauge hog rings on twenty-four
(24) inch centers. Coating shall match coating of fabric furnished.
V. TOP RAIL
1-5/8" OD Schedule 40 galvanized pipe, or 1-5/8" x 4" galvanized roll section.
Fabric to be tied to top rail every 24" with #9 gauge aluminum tie wires.
VI. BRACES
Same material as top rail and trussed from line post back to terminal post
with 3/8" galvanized rod complete with truss tightener.
VII. LINE POSTS
Galvanized Hi Carbon 1.875" H-Column or 2-3/8" OD Schedule 40 pipe, spaced
on centers not to exceed ten (10) feet. Post equipped with #6 gauge gal-
vanized clips on. fourteen (14) inch centers.
-111. EXTENSION ARMS
Line post extension arms to withstand a minimum pull down weight of 450 lbs.
from end of arm and are to be made of pressed steel or malleable iron base
- 1 -
with pressed steel extension riveted and galvanized after assembly.
IX. TERMINAL POSTS
End, corner, and pull posts to be 2-7/8" OD Schedule 40 galvanized pipe, or
31" x 31" galvanized roll formed section. Fabric to be attached to terminal
posts by use of T' x 3/4" tension bars laced to post every 14" with•11 gauge
1" wide steel bands and 3/8" diameter bolts and nuts, or by integrally weav-
ing wire to post in formed lock loops. Pipe posts -to have cast iron or ,
pressed steel top of manufacturer's standard design.
X. GATE POSTS
Maximum opening 6' single or 12' double - 277/8" OD Schedule 40 galvanized
pipe, or 31" x 31" galvanized roll section. Maximum opening 12' single or
24' double - 4" OD galvanized pipe weight 9.11#1 per ft. Maximum' opening 18'
single or 36' double - 6-5/8" OD galvanized pipe weight 18.971 per ft. Over
18' single or 36' double - 8-5/8" OD galvanized pipe weight.
XI. GATES
Frame to be 2" OD galvanized pipe with pressed steel or malleable .iron corner
ells riveted with 4 rivets per corner. Internal bracing shall be 1-3/8" OD
pipe with 3/8" adjustable truss rods. Gate shall be complete with padlocking
device, center rest and semi -automatic catch to secure drive gate in open
position.
XII. TOLERANCE
Standard Mill Tolerances on all framework members and chainilink fabric apply.
XIII. ERECTION
Fence to be installed by skilled and experienced fence erectors and on lines
and grades furnished by owner. All line posts to be set in concrete founda-
tion a minimum of 9" diameter and a minimum of 30" deep. Gate posts shall
be set in concrete foundation a minimum of 3 times the diameter of the post
1-2-4 concrete mixture.
- 2 -
PROPOSED CHAIN LINK FENCE
LUBBOCK, TEXAS
3125183
N.E.B.
/"= 60'
DWG. NO.
SD - 0001 - 9-033183
DATE
DRAWN
APPROVED
SCALE
SECTION_CORNER
�: f SECTION LINE N 89040'E (I I/Z PIPE i
160'
so. 0 37.5'
260�.
X .. — X— —it
89055 9CP05' a _
I PROPOSED GATE
S
x EXISTING
I I CITY WELL
I NO. 32
I 3
o� z
I
44 X
J
PROPOSED I
CHAIN LINK FENCE NORMPROPOSED GATE I p
C W
11500638" a cn
i
X • = EXISTING 1/2" REBAR
x
�X
gi, _
6405922" X/
Y /
x
RESOLUTION 4491 5/12/83
Cal T Y RFTARY-TREASURER
IDGV:cl
I
IBE IT RESOLVED BY THE CITY COUNCIL OF THE CI'
THAT the Mayor of the City of Lubbock B:
directed to execute for and on behalf of the
!Cyclone Fence Sales for a substation fence, ,
I9-033183, pursuant to Bid Number 7349, said
(between said City as the prospective owner ai
contractor for such construction. The state.
$8,260.00, attached herewith which shall be
Council and as spread upon the minutes of th
a part of this Resolution as if fully copied
(Passed by the City Council this 12th day o
ALAW HE
ATTEST:
ti
Evelyn Ga ga, City Secr ary-Treasurer
APPROVED AS TO CONTENT:
C
Carroll McDonald, Director of
Electric Utilities
APPROVED AS TO FORM: .
D&r Vandiv%f, First. Assistant City Attorney
RESOLUTION 139 1- 5/12/83
CONTRACT AGREEMENT
(EQUIPMENT)
THIS AGREEMENT, made and entered into this 12th day of May
19 83 , by and between The City of Lubbock, Texas acting through its Mayor and
City Council thereunto duly authorized so to do, Party of the First Part, and
hereinafter called the Purchaser, and _ Cyclone Fence Sales , a
corporation of Texas Party of the Second Part, and
hereinafter called the Contractor.
WITNESSETH:
THAT WHEREAS, the Purchaser has caused to be prepared, in accordance with
law, specifications, plans, and other contract documents for the work herein
described, and has approved and adopted said documents, and has caused to be
published, in the manner and for the time required by law, an advertisement
for and in connection with acquiring Substation Fence in accordance with
the terms of this Contract; and
WHEREAS, the said Contractor, in response to such advertisement, has
submitted to the Purchaser, in the manner and at the time specified, a sealed
proposal in accordance with the terms of said advertisement; and
WHEREAS, the Purchaser, in the manner prescribed by law, has publicly
opened, examined, and canvassed the proposals submitted in response to the
published invitation therefor, and as a result of such canvass has determined
and declared the aforesaid Contractor to be the best bidder for the said work
and has duly awarded to the said Contractor a contract therefor, for the sum
or sums named in the Contractor's proposal, a copy thereof being attached to
and made a part of this Contract.
NOW THEREFORE, in consideration of the compensation to be paid to the
Contractor and of the mutual agreements herein contained, the Parties to these
presents have agreed and hereby agree, the Purchaser for itself and its successors,
and the Contractor for itself, himself, or themselves, or its, his, or their
successors and assigns, or its, his, or their executors and administrators, as
follows:
ARTICLE I. That the Contractor shall (a) Furnish all materials,
supplies, and equipment specified and required to be incorporated in and'form a
permanent part of the completed work; (b) Provide and perform all necessary
work; and, in a good, substantial, and workmanlike manner and in accordance
with the provisions of the General Conditions, and the Instructions to Bidders,
(which are attached hereto and made a part hereof) and in conformity with the
Specifications Number SE-0001-9-033183 (c) Execute and complete all work
included in and covered by the Purchaser's official award of this Contract to
the said Contractor, such award being based on the acceptance by the Purchaser
of the Contractor's proposal, or part thereof, as follows:
Substation Fence
ARTICLE II. That the Purchaser shall pay to the Contractor for the
}yerformance of the work embraced in this Contract, and the Contractor will
accept as full compensation therfor, the sum (subject to adjustment as pro-
vided by the Contract) of _Eight thousand two hundred sixty dollars
($ 8.260.00 )
for all work covered by and included in the Contract award and designated in
the foregoing Article I.
ARTICLE III.- The Contractor shall proceed with the work to be performed
under the provisions of.this Contract on, or within ten (10) days following,
the date of public acceptance of the Contractor's proposal by the Purchaser.
Contractor shall not delay the start of the work to be performed under the
provisions of this Contract except by written order from the Purchaser.
Contractor shall complete said work by. July 1st, 1983
IN WITNESS -WHEREOF, the Parties hereto have executed this. Contract as of
day and year first written.
CITY OF LUBBOCK
BY:
ATTEST:
Evelyn Ga fga, City S c ary-Treasurer
APPROVED AS TO CONTENT:
G� �i�"lc�lCic�
APPROVED AS TO FORM:
I}ONA G..VANDIVER,--Assistant City -Attorney
PARTY OF THE SECOND PART (CONTRACTOR)
BY:
ATTEST: Signature of Officer
CO-21thcrI mew 14 A.'uA, G6-2t
Secretary Title
NOTE: This Contract must be signed by the President or Vice President of the
Contractor's firm and attested by the Secretary of the firm. If the Contract
is to be signed by any person other than the President or lice President, then
a Board Resolution authorizing said person to sign and bind the firm must be
included with each copy of the Contract.
i, Donald C. Anderson , Assistant Secretary of United States Steel
Corporation, a Delaware corporation, do hereby certify that the following
is a true and correct copy of a resolution adopted by the Corporate Policy
Committee of said United States Steel Corporation on the 22nd day of
December, 1980,.and that said resolution is in full force and effect at
this date:
RESOLVED: That the Managing Director and any Sales
Manager of Manufactured Wire Products; the General Manager
of Electrical Cable; the General Manager and any Manager -Sales,
Area Sales Manager, Sales Representative and Service Representative
of Wire Rope; the General Manager, the Manager and any Sales,
District, Assistant District and Contracting Manager of Cyclone
Fence, be, and each of them hereby is, authorized and empowered
for and on behalf of this Corporation to execute any and all
tenders, proposals, order acceptances, contracts and other
documents relating to the sale of products or services of this
Corporation within their respective commercial responsibilities.
Witness my hand and seal of the Corporation this day of 19
Assistant Secretary
STANDARD CHAIN LINK FENCE SPECIFICATIONS
9
1. STYLE FENCE
Chain link fence with three strands of barbed wire on 450 extension arms.
Fence to be nine (9) feet high overall when erected.
11. FABRIC
Steel wire to be ninety-six (96) inches high, #9 gauge woven in a two (2)
inch mesh with barbed selvages top and bottom. The wire pickets shall stand
a minimum tensile strength of 80,000 PSI based on a cross sectional area of
wire.
111. PROTECTIVE COATING
The chain link fabric shall be either galvanized after weaving or aluminum
coated. Galvanizing shall be 2 oz. per sq. ft. of area in accordance with
ASTM A392 Class II. Aluminum coating shall be .40 oz. per sq. ft. of area
in accordance with ASTM A491-63-T.
IV. BOTTOM TENSION WIRE S BARBED WIRE
Steel barbed wire to be of 4 point pattern composed of two strands of 121
^, gauge line wires with 14 gauge barbs spaced on approximately five (5) inch
centers. Bottom tension wire shall be No. 7 gauge spring coil tension wire,
fastened to chain link fabric with No. 11 gauge hog rings on twenty-four
(24) inch centers. Coating shall match coating of fabric furnished.
V. TOP RAIL
1-5/8" OD Schedule 40 galvanized pipe, or 1-5/8" x 4" galvanized roll section.
Fabric to be tied to top rail every 24" with #i9 gauge aluminum tie wires.
VI. BRACES
Same material as top rail and trussed from line post back to terminal post
with 3/8" galvanized rod complete with truss tightener.
VII. LINE POSTS
Galvanized Hi Carbon 1.875" H-Column or 2-3/8" OD Schedule 40 pipe, spaced
on centers not to exceed ten (10) feet. Post equipped with #6 gauge gal-
vanized clips on- fourteen (14) inch centers.
EXTENSION ARMS
Line post extension arms to withstand a minimum pull down weight of 450 lbs.
from end of arm and are to be made of pressed steel or malleable iron base
- 1 -
with pressed steel extension riveted and galvanized after assembly.
Y
IX. TERMINAL POSTS
End, corner, and pull posts to be 2-7/8" OD Schedule 40 galvanized pipe, or
3}" x 31" galvanized roll formed section. Fabric to be attached to terminal
posts by use of 4" x 3/4" tension bars laced to post every 14" with•11 gauge
1" wide steel bands and 3/8" diameter bolts and nuts, or by integrally weav-
ing wire to post in formed lock loops. Pipe posts -to have cast iron or
pressed steel top of manufacturer's standard design.
X. GATE POSTS
Maximum opening 6' single or 12' double - 277/8" OD Schedule 40 galvanized
pipe, or 31" x 31" galvanized roll section. Maximum opening 12' single or
24' double - 4" OD galvanized pipe weight 9.11# per ft. Maximum opening 18'
single or 36' double - 6-5/8" OD galvanized pipe weight 18.97# per ft. Over
18' single or 36' double - 8-5/8" OD galvanized pipe weight.
XI. GATES
Frame to be 2" OD galvanized pipe with pressed steel or malleable .iron corner
ells riveted with 4 rivets per corner. Internal bracing shall be 1-3/8" OD
pipe with 3/8" adjustable truss rods. Gate shall be complete with padlocking
device, center rest and semi -automatic catch to secure drive gate in open
position.
XII. TOLERANCE
Standard Mill Tolerances on all framework members and chainilink fabric apply.
XIII. ERECTION
Fence to be installed by skilled and experienced fence erectors and on lines
and grades furnished by owner. All line posts to be set in concrete founda-
tion a minimum of 9" diameter and a minimum of 30" deep. Gate posts shall
be set in concrete foundation a minimum of 3 times the diameter of the post
1-2-4 concrete mixture.
2 - `
Mr— 00001/41 IVIN
PROPOSED CHAIN LINK FENCE
LUWlUU rr% rvYVCli Cl LIU r
LUBBOCK, TEXAS
3125163
N.E.B.
1 = 60
DWG. NO.
SD — 0001 — 9—033183
DATE
DRAWN
APPROVED
SCALE
SECTIQN CORNER
SECTION LINE N 89040'E ( 1 1/2� PIPE)
160�
0
-- X -- X X' .. — X — X-11
x890 55' 90°05� a
I � PROPOSED GATE ( x EXISTING
CITY WELL
IX NO. 32
I
I ti
X oS
X
44 I
(—PROPOSED
CHAIN LINK FENCE NORTH PROPOSED GATE �'i1
X c
I
11500C 38" aoc-i
Iiir
X • o EXISTING 1/2" RESAR
x
/X
/ X• 2e6 '` eFVk
x 64059�22" X�
.(0711
NOTICE TO BIDDERS
Sealed proposals addressed to Gene Eads, Director of Purchasing,
City of Lubbock, Texas, will be received at the office of the
Purchasing Agent until 4:00 P.M. on April 25, 1983 ,
for furnishing and installing all necessary materials, machinery,
equipment, superintendence, and labor for construction of a
substation fence in accordance with the attached specifications.
The City Council will consider bids on May 12, 1983
at the City Hall, subject to the right to reject any or all bids
and to waive formalities. Bids may not be withdrawn after they are
submitted. Bidders are required to submit a cashier's or certified
check or bid bond in the amount of 5% of the total bid and the
successful bidder shall provide bond in the full amount of the
contract price executed by a surety company authorized to do
business in Texas.
CITY OF LUBBOCK, TEXAS
M.
Gene Eads
Director of Purchasing
CERTIFICATE OF INSURANCE
TO: CITY OF LUBBOCK Date
Type of
Lubbock, Texas Project:
THIS IS TO CERTIFY THAT
(Name and Address of Insured)
is, at the date of this certificate, insured by this Company with respect to the business
operations hereinafter described, for the types of insurance and in accordance with the
provisions of the standard policies used by this Company, and further hereinafter des-
cribed. Exceptions to standard policy noted on reverse side hereof. '
TYPE OF INSURANCE ,.
Policy No. Effective Expires Limits of Liability
Workmen's
Compensation
Contractor's Protec- 1 person $
tive Contingent 1 accident $
Liability Property Damage $
Builder's .
Risk
Automobile 1 person $
1 accident $
Other Property Damage $
The foregoing Policies (do) (do not) cover all sub -contractors.
'Locations Covered:
DESCRIPTIO14 of Operations Covered
The above policies either _in the body thereof or by appropriate endorsement provide
that they nay not be changed or cancelled by the insurer' in less than the legal time
required after the insured has received written notice of such change or cancellation,
or in case there is no legal requirement, in less than five days after the insured has
received such written notice.
FIVE COPIES OF THIS CERTIFICATE.
MUST En SENT TO THE OWNER
By
Title
(Name of insurer)
TABLE OF CONTENTS
Notice To Bidders
Certificate of Insurance
Contract Agreement
Specifications
P. 0. Box 5466
USS Cyclone Fence Arlington, Texas 76011
VWUd IWa SW cffpr" [ 817 ] 261-6206
TOj City of Lubbock
Purchasing Department
P. 0. Box 2000
Lubbock, Texas 79457
sUBJECTs Lubbock Power & Light Sub Station
Please process/review the enclosed item[s]
[ ] Proposal
[ ] Proposal for your signature
[ ] Confirmation of verbal
Quotation
[ ] Confirmation of your
verbal order
[ ] Confirmation of your
Purchase Order No,
( ] Acknowledgement copy of
your P.O. No.
[XM Signed contracts and insurance
REMARKSs
Yours truly,
Eddie Cromwell
cc$
[ ] CycloneTM General Catalog
[ ] Aluminum Coated Fabric Data
[ ] CycloneTM Drawings]
[ ] Electric Gate Operator Data
We want to work for you.
LTerminal Post
I Line Post
C Line Post
C Line Post
13 Rail
,
NAME AND ADDRESS OF AGENCY
COMPANIES AFFORDING
,.,,}1�� LpE`-�� ^
LJ1 11�'.,/
Marsh 6 •McLennan, Inc.
COVERAGES t./ V
Suite 5500
COMPANY %�
LETTER A Employers
Casualty Company
600 Grant Street
COMPANY
LETTER B Insurance
Company of North America
Pittsburgh, PA 15219
NAME ANq ADDRESS OF INSURED
e
Cyclone Fence
COMPANY
LETTER
Manufactured Wire Products Division
United States Steel Corporation
PA
ETtER"Y
Post Office Box 7310
Chicago, Illinois 60680
LEETTERNY E
This is to certify that policies of insurance listed below have been Issued to the insured named above and are in force at this time.
Notwithstanding any requirement, term or condition
of any contract or other document with respect to which this certificate may be issued or may pertain, the insurance afforded
by the policies described herein is subject to all the
terms_ exclusions and conditions of such policies.
Limits o L a it
n Thousands
COMPANY
LETTER
TYPE OF INSURANCE
POLICY NUMBER
POLICY
EXPIRATION DATE
EACH
OCCURRENCE
-AGGREGATE
GENERAL LIABILITY
BODILY INJURY
s
s
A
®COMPREHENSIVE FORM
CGL 573881
5/l/86
EIPREMISES—OPERATIONS
PROPERTY DAMAGE
s
Z:
'
®EXPLOSION AND COLLAPSE.
HAZARD
®
UNDERGROUND HAZARD
® PRODUCTS/COMPLETED
OPERATIONS HAZARD
® CONTRACTUAL INSURANCE
-.
BODILY INJURY AND
PROPERTY DAMAGE
s5,000
s5,000
BROAD FORM PROPERTY
COMBINED
DAMAGE
®
INDEPENDENT CONTRACTORS
_ PERSONAL INJURY
$ S , OOO
-
® PERSONAL INJURY
AUTOMOBILE LIABILITY
BODILY INJURY
$
-
B
®
SRL 706
5/l/86
(EACH PERSON)
COMPREHENSIVE FORM
BODILY INJURY
$
®
(EACH ACCIDENT)
OWNED
PROPERTY DAMAGE
S
®
HIRED
BODILY INJURY AND
® NON -OWNED
PROPERTY DAMAGE
$ 5,000
COMBINED
EXCESS LIABILITY
BODILY INJURY AND
❑ UMBRELLA FORM
PROPERTY DAMAGE
s
$
❑ OTHER THAN UMBRELLA
COMBINED
FORM
WORKERS' COMPENSATION
Various
STATUTORY
A
and
Idaho, New Mexico, Texas
l/l/86
: 100
EMPLOYERS' LIABILITY
tCACN.COOIN
OTHER
DESCRIPTION OF OPERATIONS/LOCATIONS/VEHICLES ±
Cyclone Office Location: Fort Worth
furnish and install chain link fencing at Lubbock Power and
Light Substation, Municipal Drive & Guava St., Lubbock, Tx., USS#519-3-00246
Cancellation:- Should any of the above described policies be cancelled before the expiration date thereof, the issuing com-
pany will endeavor to mail P days written notice to the below named certificate holder, but failure to
mail such notice shall impose no obligation or liability of any kind upon the company.
NAME AND ADDRESS OF CERTIFICATE HOLDER:
City of Lubbock
L P. 0. Box 2000
Lubbock, Texas 79457
DATE ISSUED May 23 1983
AUTHORIZED REPRESENTATIVE
ACORD 25 (1-79)